CALGreen July 2012 Non-Residential: 5.503 – FIREPLACES

 Comments Off on CALGreen July 2012 Non-Residential: 5.503 – FIREPLACES
Dec 092012
 

 

SECTION 5.503 – FIREPLACES

 

CALGreen Section: 5.503.1 General. Install only a direct-vent sealed-combustion gas or sealed wood-burning fireplace, or a sealed woodstove or pellet stove, and refer to residential requirements in the California Energy Code, Title 24, Part 6, Subchapter 7, Section 150. Woodstoves, pellet stoves and fireplaces shall comply with applicable local ordinances.

 

5.503.1.1 Woodstoves. Woodstoves and pellet stoves shall comply with U.S. EPA Phase II

emission limits.

 

Intent:

Although limited in non-residential applications, this code provision is intended to prevent the use of indoor air for combustion and to prevent contaminated air and any unused fuel from escaping

the sealed fireplace to maintain indoor air quality and increased energy efficiency.

 

Existing Law or Regulation:

Currently the California Energy Code, CCR, Title 24, Part 6, Subchapter 7, Section 150 regulates residential fireplaces. There may be a local or regional ordinance in place.

 

Compliance Method:

1.   Specify and install a direct-vent gas fireplace

2.   Specify and install a pellet or wood stove which meets the US EPA Phase II emission standards.

3.   Comply with local or regional ordinance.

 

Suggestion:

Contractor: Retain product data sheets for onsite verification by the enforcing agency and for the operation and maintenance manual.

 

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans and specifications to confirm that the fireplaces and/or woodstoves meet the direct-vent sealed-combustion and/or US

EPA Phase II emission limits.

 

On-Site Enforcement: The inspector should review the permit set of plans and product data sheets to verify that the fireplaces and/or woodstoves as specified on the approved plans and specifications are installed, or are stored on site with the ability to be verified

SECTION 5.714.3 – FIREPLACES

 

CALGreen Section: 5.714.3.1 General. Install only a direct-vent sealed-combustion gas or sealed wood-burning fireplace, or a sealed woodstove or pellet stove, and refer to residential requirements in the California Energy Code, Title 24, Part 6, Subchapter 7, Section 150. Woodstoves, pellet stoves and fireplaces shall comply with applicable local ordinances.

5.714.3.1.1 Woodstoves. Woodstoves and pellet stoves shall comply with U.S. EPA Phase II

emission limits.

 

Intent:

CBSC adopted this section from the new construction division to provide clarity to the code user regarding the use of gas and wood burning appliances listed in this section for additions or alterations. As rarely-used amenities in new nonresidential construction, they are not required for

heat but are typically installed for effect.

 

Compliance and Enforcement: See § 5.503 of this guide

CALGreen July 2012 Non-Residential: 5.504.1.3 Temporary ventilation.

 Comments Off on CALGreen July 2012 Non-Residential: 5.504.1.3 Temporary ventilation.
Dec 092012
 

CALGreen Section: 5.504.1.3 Temporary ventilation. The permanent HVAC system shall only be used during construction if necessary to condition the building within the required temperature range for material and equipment installation. If the HVAC system is used during construction, use return air filters with a Minimum Efficiency Reporting Value (MERV) of 8, based on ASHRAE 52.2 1999, or an average efficiency of 30% based on ASHRAE 52.1 1992. Replace all filters immediately prior to occupancy.

 

Intent of new section for 2012:

The intent of this new section is for mandatory compliance, taken from voluntary Section A5.504.1.1, Item 3, which allows limited use of the permanent heating and cooling system during construction and requires the use of air filters with a Minimum Efficiency Reporting Value (MERV) of 8. It is intended to control air pollutants for workers during construction and ensure good air quality for occupants when the building is turned over to the owner. It allows ventilation using air conditioning systems if necessary, though this practice is noted not to be an optimum choice due to possible damage to equipment that may jeopardize a warranty.

 

Existing Law or Regulation:

The California Energy Code, CCR, Part 6 contains ventilation standards for conditioned spaces. CCR, Title 8 contains additional regulations for the protection of worker safety.

 

Compliance Method:

Engineers and designers should include the measures intended to promote air quality in the project specifications for ventilation, materials and others as applicable. The contractor should be responsible for employing them on the job and being able to demonstrate that the practices are being followed if requested by the enforcing agency.

 

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans and specifications for directions on ventilation practices to be followed by the contractor.

 

On-Site Enforcement: The inspector should review the permit set of plans to verify which air quality practices the contractor is to use on the project and ask for demonstration of their employment during site visits.

 


CALGreen Section: 5.714.4.1 Temporary ventilation. The permanent HVAC system shall only be used during construction if necessary to condition the building within the required temperature range for material and equipment installation. If the HVAC system is used during construction, use return air filters with a Minimum Efficiency Reporting Value (MERV) of 8, based on ASHRAE 52.2 1999, or an average efficiency of 30% based on ASHRAE 52.1 1992. Replace all filters immediately prior to occupancy.

 

Intent:

This new section for mandatory compliance for newly constructed buildings, taken from Section A5.504.1.1, Item 3, allows limited use of the permanent heating and cooling system during construction of additions and areas of alteration. It requires the use of air filters with a Minimum Efficiency Reporting Value (MERV) of 8 and is intended to control air pollutants for workers during construction and ensure good air quality for occupants.

 

 

Compliance and Enforcement: See § 5.504.1.3 of this guide

CALGreen July 2012 Non-Residential: 5.504.3 Covering of duct openings and protection of mechanical equipment during construction.

 Comments Off on CALGreen July 2012 Non-Residential: 5.504.3 Covering of duct openings and protection of mechanical equipment during construction.
Dec 092012
 

CALGreen Section: 5.504.3 Covering of duct openings and protection of mechanical equipment during construction. At the time of rough installation and during storage on the construction site until final startup of the heating, cooling and ventilating equipment, all duct and other related air distribution component openings shall be covered with tape, plastic, sheet metal or other methods acceptable to the enforcing agency to reduce the amount of dust, water and debris which may enter the system.

Intent:

To enhance HVAC equipment efficiency and indoor air quality at building occupancy by preventing construction debris from building up in the air ducts during construction.

Change for 2012: CBSC is proposing to modify this section in concert with HCD, in response to comments made by CARB, to clarify for the code user when protection is needed, which equipment to protect, and against what pollutants ducts should be sealed.

Existing Law or Regulation:

The California Energy Code, CCR, Part 6 contains ventilation standards for conditioned spaces. CCR, Title 8 contains additional regulations for the protection of worker safety.

Compliance Method:

Engineers and designers should include the measures intended to promote air quality in the project specifications for ventilation, materials and others as applicable. The contractor should be responsible for employing them on the job and being able to demonstrate that the practices are being followed if requested by the enforcing agency.

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans and specifications for directions on ventilation practices to be followed by the contractor.

On-Site Enforcement: The inspector should review the permit set of plans to verify which air quality practices the contractor is to use on the project and ask for demonstration of their employment during site visits.

CALGreen Section: 5.714.4.3  Covering of duct openings and protection of mechanical equipment during construction. At the time of rough installation and during storage on the construction site until final startup of the heating, cooling and ventilating equipment, all duct and other related air distribution component openings shall be covered with tape, plastic, sheet metal or other methods acceptable to the enforcing agency to reduce the amount of dust, water and debris which may enter the system.

Intent:

To enhance HVAC equipment efficiency and indoor air quality at building occupancy by preventing construction debris from building up in the air ducts during construction. CBSC adopted this section for applicable additions and alterations as modified for new construction. The purpose is to protect building occupants from indoor pollution from HVAC equipment

operation and to protect the equipment against damage.

Compliance and Enforcement: See § 5.504.3 of this guide

CALGreen July 2012 Non-Residential: 5.504.4 Finish material pollutant control.

 Comments Off on CALGreen July 2012 Non-Residential: 5.504.4 Finish material pollutant control.
Dec 092012
 

CALGreen Section: 5.504.4 Finish material pollutant control. Finish materials shall comply

with Sections 5.504.4.1 through 5.504.4.4.

 

5.504.4.1 Adhesives, sealants, and caulks. Adhesives, sealants, and caulks used on the project shall meet the requirements of the following standards:

 

1. Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers and caulks shall comply with local or regional air pollution control or air quality management district rules where applicable, or SCAQMD Rule 1168 VOC limits, as shown in Tables

5.504.4.1 and 5.504.4.2. Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene, and trichloroethylene), except for aerosol products as specified in subsection 2, below.

 

2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking compounds (in units of product, less packaging, which do not weigh more than one pound and do not consist of more than 16 fluid ounces) shall comply with statewide VOC standards and other requirements, including prohibitions on use of certain toxic compounds, of California Code of Regulations, Title 17, commencing with Section 94507.

 

Tables not shown – refer to Code

 

5.504.4.3 Paints and coatings. Architectural paints and coatings shall comply with VOC limits in Table 1 of the ARB Architectural Coatings Suggested Control Measure, as shown in Table

5.504.4.3, unless more stringent local limits apply. The VOC content limit for coatings that do not meet the definitions for the specialty coatings categories listed in Table 5.504.4.3, shall be

determined by classifying the coating as a Flat, Nonflat, or Nonflat-High Gloss coating, based

on its gloss, as defined in subsections 4.21, 4.36, and 4.37 of the 2007 California Air

Resources Board Suggested Control Measure, and the corresponding Flat, Nonflat, or Nonflat- High Gloss VOC limit in Table 5.504.4.3 shall apply.

 

5.504.4.4 Carpet systems. All carpet installed in the building interior shall meet the testing and product requirements of one of the following:

1. Carpet and Rug Institute’s Green Label Plus Program.

2. California Department of Public Health Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers, Version 1.1, February 2010 (also known as Specification 01350).

3. NSF/ANSI 140 at the Gold level or higher.

4. Scientific Certifications Systems Sustainable Choice.

 

5.504.4.4.1 Carpet cushion. All carpet cushion installed in the building interior shall meet the requirements of the Carpet and Rug Institute’s Green Label program.

 

5.504.4.4.2 Carpet adhesive. All carpet adhesive shall meet the requirements of Table

5.504.4.1.

 

5.504.4.5 Composite wood products. Hardwood plywood, particleboard, and medium density fiberboard composite wood products used on the interior or exterior of the building shall meet the requirements for formaldehyde as specified in CARB’s Air Toxics Control Measure for Composite Wood (17 CCR 93120 et seq.), by or before the dates specified in those sections,

as shown in Table 5.504.4.5.

Table not shown – refer to Code

5.504.4.5.1 Early compliance. Reserved.

 

5.504.4.5.2 Documentation. Verification of compliance with this section shall be provided as requested by the enforcing agency. Documentation shall include at least one of the following:

1. Product certifications and specifications

2. Chain of custody certifications standards

CalGreen July 2012 Non-Residential: 5.504.4.6. Resilient flooring systems.

 Comments Off on CalGreen July 2012 Non-Residential: 5.504.4.6. Resilient flooring systems.
Dec 092012
 
5.504.4.6. Resilient flooring systems. For 50 percent of floor area receiving resilient flooring, install resilient flooring complying with the VOC-emission limits defined in the 2009

Collaborative for High Performance Schools (CHPS) criteria and listed on its High Performance

Products Database; products compliant with CHPS criteria certified under the Greenguard Children & Schools program; certified under the Resilient Floor Covering Institute (RFCI) FloorScore program; or meet California Department of Public Health 2010 Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers, Version 1.1, February 2010 (also known as Specification 01350.)

 

[DSA-SS] Documentation shall be provided that verifies that finish materials are certified to meet the pollutant emission limits.

 

5.504.4.6.1 Verification of compliance. Documentation shall be provided verifying that resilient flooring materials meet the pollutant emission limits.

 

 

Intent:

The purpose of these measures is to reduce the volatile organic compounds (VOC) of finish materials commonly installed on a project, which will help improve air quality for the building occupants.

 

Change for 2012: Most of the changes proposed for this division resulted from comments received from CARB. They are intended to provide clarity and accuracy for the code user.

 

Sections 5.504.4.4 Carpet systems and 5.504.4.3.1 Carpet cushion. CBSC has updated the referenced standards as suggested by CARB to their current names. The standard for NSF/ANSI 140 “Gold” is also tagged as a minimum standard, not an absolute, for clarity.

 

Section 5.504.4.4.2 Documentation [for composite wood products]. This section is modified in response to comments by CARB to clarify for the code user the qualifying product certifications.

 

Section 5.504.4.6 Resilient flooring systems. CBSC is proposing updating the referenced standards as suggested by CARB to their current names, including a reference to Greenguard-certified products previously cited in a note.

 

Existing Law or Regulation:

The low-VOC provisions are based on the recommendations, guidelines and regulations of the

Air Resources Board cited in each section. Regulations for aerosol adhesives and paints and for composite wood products are found in California Code of Regulations, Title 17 as noted above.

 

Compliance Method:

Specify finish materials that meet the limits of VOC shown in the tables for adhesives and sealants, paints and coatings, and composite wood products (particle board and hardboard

casework). Flooring products (carpet systems and resilient flooring) shall be specified to meet

VOC limit criteria as tested by the listed organizations. Substitutes may be approved by the local enforcing authority if it deems equivalency.

 

Suggestion:

Contractor: Retain product data sheets for onsite verification by the enforcing agency and for the operation and maintenance manual. Sample compliance forms can be found in Part 4 of this

Guide.

 

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans and specifications to confirm that the finishes are specified to meet VOC emission limits.

 

On-Site Enforcement: The inspector should review the permit set of plans and product data sheets maintained by the contractor to verify finishes specified on the approved plans and specifications are installed, or at least stored on site with the ability to be verified. The inspector may review data on material containers or specifications provided with products or accept self- certification form.

 

CALGreen Section: 5.714.4.4 Finish material pollutant control.

 

Finish materials shall comply with Sections 5.714.4.4.1 through 5.714.4.4.6

Public Health 2010 Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers, Version 1.1, February 2010 (also known as Specification 01350.)

 

 

Intent:

The purpose of these measures is to reduce the volatile organic compounds (VOC) of finish materials commonly installed on an addition and alteration project, which will help improve air quality for the building occupants as for new construction in Division 5.5. During rulemaking and

publication, an error was made in the referenced sections. They should read “Sections

5.714.4.4.1 through 5.714.4.4.6, up to and including resilient flooring systems.

 

Compliance and Enforcement: See § 5.504.4.4 through § 5.504.4.6 of this guide

CalGreen July 2012 Non-Residential: 5.504.5.3 Filters.

 Comments Off on CalGreen July 2012 Non-Residential: 5.504.5.3 Filters.
Dec 092012
 

CALGreen Section: 5.504.5.3 Filters. In mechanically ventilated buildings, provide regularly occupied areas of the building with air filtration media for outside and return air that provides at least a Minimum Efficiency Reporting Value (MERV) of 8. MERV 8 filters shall be installed

prior to occupancy, and recommendations for maintenance with filters of the same value shall be included in the operation and maintenance manual.

 

Exception: A MERV-1 filter shall be allowed for return air only or return with prefiltered outside air if the filter is of a re-usable, non-disposable type, and the fan energy use of that air delivery system is 0.4W/cfm or less at design airflow.

 

Intent:

The intent of this regulation is to filter particulate matter from the air by the use of at least MERV

8-rated filters for improved air quality.

 

Change for 2012: CBSC is proposing modification of this section providing clarity for the code user to emphasize that MERV 8 filters are to be installed prior to occupancy and that their replacement with like filters should be a recommendation for operation of a building. (See also Section 5.504.1.3, above.) Also, in response to comment, an exception has been added for certain ductless HVAC equipment which is incompatible with the MERV 8 filter requirement, but which is highly efficient and provides other benefits to a building operator or occupant.

 

Existing Law or Regulation:

There is NO current law or regulation for this code provision.

 

Compliance Method:

Specify and install prior to occupancy at least MERV 8 filters for the return air grilles.

 

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans and specifications to confirm that the filters are specified to meet MERV 8, or that specified equipment qualifies for the

exception.

 

On-Site Enforcement: The inspector should review the permit set of plans and product data sheets maintained by the contractor to verify that HVAC filtration specified on the approved plans and specifications are installed, or are stored on site with the ability to be verified. The inspector may check a sample of installed filters to verify the MERV rating.

 

 

CALGreen Section: 5.714.4.6.1 Filters. In mechanically ventilated buildings, provide regularly occupied areas of the building with air filtration media for outside and return air that provides at least a Minimum Efficiency Reporting Value (MERV) of 8. MERV 8 filters shall be installed

prior to occupancy, and recommendations for maintenance with filters of the same value shall be included in the operation and maintenance manual.

 

Exception: A MERV-1 filter shall be allowed for return air only or return with prefiltered outside air if the filter is of a re-usable, non-disposable type, and the fan energy use of that air delivery system is 0.4W/cfm or less at design airflow.

 

Intent:

The intent of this regulation is to filter particulate matter from the air by the use of at least MERV

8-rated filters for improved air quality.

 

Change for 2012: CBSC adopted this section and exception as applicable to additions and alterations as modified for new construction to provide clarity for the code user to emphasize that MERV 8 filters are to be installed prior to occupancy and that their replacement with like filters should be a recommendation for operation of a building. It proposes the same exception for highly energy-efficient ductless HVAC equipment.

 

Compliance and Enforcement: See § 5.504.5.3 of this guide

CalGreen July 2012 Non-Residential: 5.504.7 Environmental tobacco smoke (ETS) control

 Comments Off on CalGreen July 2012 Non-Residential: 5.504.7 Environmental tobacco smoke (ETS) control
Dec 092012
 

CALGreen Section: 5.504.7 Environmental tobacco smoke (ETS) control. Where outdoor areas are provided for smoking, prohibit smoking within 25 feet of building entries, outdoor air intakes and operable windows and within the building as already prohibited by other laws or regulations; or as enforced by ordinances, regulations, or policies of any city, county, city and county, California Community College, campus of the California State University, or campus of the University of California, whichever are more stringent. When ordinances, regulations, or policies are not in place, post signage to inform building occupants of the prohibitions.

 

Intent:

By prohibiting smoking in buildings, and in those instances where outdoor areas are and dedicated for the use of smokers, this provision is intended to improve indoor air quality and to

protect non-smokers from second hand smoke.

 

Change for 2012: CBSC is proposing a minor change in response to comment from CARB to recognize that other laws and regulations may apply to smoking in and around buildings. Smoking is a public health issue that is within the authority of California Department of Public Health, and currently the Labor Code allows smoking in certain workplaces. Building codes are intended to regulate construction and installation of building appurtenances, not building operations or occupant behavior.

 

Existing Law or Regulation:

State law prohibits smoking inside most buildings, and many local jurisdictions and college campuses have regulations that require a certain distance that smoking can occur outside a

building. AB 1807 (Stats. 1983, c. 1047) is the public policy of the state that emissions of toxic air

contaminants should be controlled to levels which prevent harm to the public health.

 

Compliance Method:

Include in the signage specification and post signs that prohibit smoking for an outdoor smoking area within 25 feet of building entries, outdoor air intakes and operable windows where they

occur.

 

Suggestion: In order to clarify sign placement and smoking area(s), show on one or all of the following plans: Site Plan, Floor Plan, Elevations and/or Detail Sheet.

 

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans and specifications to confirm that, if an outdoor smoking area is shown, signage is specified and located.

 

On-Site Enforcement: The inspector should review the permit set of plans against the outdoor smoking area and verify signage installed in the field.

 

CALGreen Section: 5.714.4.7 Environmental tobacco smoke (ETS) control. Where outdoor areas are provided for smoking, prohibit smoking within 25 feet of building entries, outdoor air intakes and operable windows and within the building as already prohibited by other laws or regulations; or as enforced by ordinances, regulations, or policies of any city, county, city and county, California Community College, campus of the California State University, or campus of the University of California, whichever are more stringent. When ordinances, regulations, or policies are not in place, post signage to inform building occupants of the prohibitions.

 

Intent:

By prohibiting smoking in buildings, and in those instances where outdoor areas are and dedicated for the use of smokers, this provision is intended to improve indoor air quality and to

protect non-smokers from second hand smoke.

 

Change for 2012: CBSC has adopted this section where it may apply to an addition or alteration, including a minor amendment for new construction in response to comment from CARB to recognize that other laws and regulations may apply to smoking in and around buildings.

 

 

Compliance and Enforcement: See § 5.504.7 of this guide

CalGreen July 2012 Non-Residential:5.505.1 Indoor moisture control.

 Comments Off on CalGreen July 2012 Non-Residential:5.505.1 Indoor moisture control.
Dec 092012
 

 

CALGreen Section: 5.505.1 Indoor moisture control. Buildings shall meet or exceed the provisions of California Building Code, CCR, Title 24, Part 2, Sections 1203 (Ventilation) and Chapter 14 (Exterior Walls). For additional measures not applicable to low-rise residential occupancies, see Section 5.407.2 of this code.

 

Intent:

The intent is to direct the code user to other parts of Title 24 and this part for those provisions that are intended to reduce the probability of mold and mildew growth and improve air quality.

 

Existing Law or Regulation:

California Building Code Section 1203 for attic spaces and under-floor ventilation, Chapter 14 for a weather-resistant exterior wall envelope, and Section 5.407.2.2 Entries and openings in this code.

 

Compliance Method:

Design Team: Include details on the construction plans addressing issues of moisture control,

 

Contractor: Understand and install moisture control according to construction documents and manufacturer’s installation recommendations.

 

Note:  Vapor control recommendations for different climate zones may found at www.buildingscience.com .

 

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans and specifications to confirm that moisture control features which meet Title 24 are specified and detailed.

 

On-Site Enforcement: The inspector should review the permit set of plans and confirm that moisture control measures have been incorporated into the building. Collect a copy of self- certification form if completed and signed by the contractor.

 

CALGreen Section: 5.714.7.1 Indoor moisture control. Buildings shall meet or exceed the provisions of California Building Code, CCR, Title 24, Part 2, Sections 1203 (Ventilation) and Chapter 14 (Exterior Walls). For additional measures not applicable to low-rise residential occupancies, see Section 5.407.2 of this code.

 

Intent:

CBSC adopted this section to provide clarity to the code user regarding moisture control. CBSC is proposing to include references to direct the code user to the California Building Code for general ventilation and moisture control requirements, which are intended to protect occupants

from harmful molds and mildews.

 

 

 

Compliance and Enforcement: See § 5.505.1 of this guide

CalGreen July 2012 Non-Residential: 5.506.1 Outside air delivery.

 Comments Off on CalGreen July 2012 Non-Residential: 5.506.1 Outside air delivery.
Dec 092012
 

SECTION 5.506 INDOOR AIR QUALITY

 

CALGreen Section: 5.506.1 Outside air delivery. For mechanically or naturally ventilated spaces in buildings, meet the minimum requirements of Section 121 (Requirements For Ventilation) of the 2010 California Energy Code, or the applicable local code, whichever is more stringent, and Division 1, Chapter 4 of CCR, Title 8.

 

Intent:

The purpose is to point building designers and contractors to the ventilation requirements in the

California Code of Regulations that are intended to improve indoor air quality for building occupants.

 

Existing Law or Regulation:

The California Energy Code, CCR, Title 24, Part 6, Sections 121(a) through 121(e) with flow rates as required by Table121-A. There is a possibility of a more stringent local ordinance.

 

Compliance Method:

Most engineers and contactors are familiar with following the provisions of the energy code that specify requirements for naturally and mechanically ventilated spaces, and may comply with this provision by using energy code compliance tools currently in place. Title 8 for Cal OSHA may

have additional regulations which emphasize air quality for workers in particular environments

which should be followed as required.

 

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans and specifications to confirm that building ventilation is calculated and specified to Title 24, Part 6, and if applicable,

Part 8.

 

On-Site Enforcement: The inspector should review the permit set of plans against the natural ventilation features and mechanical ventilation systems that are installed on the project, requesting results of any testing of ventilation rates. Adequate pre-occupancy building ventilation shall be verified.

 

CALGreen Section: 5. 714.7.2 Outside air delivery. For mechanically or naturally ventilated spaces in buildings, meet the minimum requirements of Section 121 (Requirements For Ventilation) of the 2010 California Energy Code, or the applicable local code, whichever is more stringent, and Division 1, Chapter 4 of CCR, Title 8.

 

Intent:

CBSC adopted this section to provide clarity to the code user regarding the mechanical or natural delivery of outdoor air to additions or areas of alteration, including references to direct the code user to the California Energy Code, Title 24, Part 6 and Title 8, Chapter 4 for requirements.

 

 

Compliance and Enforcement: See § 5.506.1 of this guide

CalGreen July 2012 Non-Residential: 5.506.2 Carbon dioxide (CO2) monitoring

 Comments Off on CalGreen July 2012 Non-Residential: 5.506.2 Carbon dioxide (CO2) monitoring
Dec 092012
 

CALGreen Section: 5.506.2 Carbon dioxide (CO2) monitoring. For buildings equipped with demand control ventilation, CO2 sensors and ventilation controls shall be specified and installed in accordance with the requirements of 2010 California Energy Code, Section 121(c).

 

Intent:

When demand control ventilation is required by Part 6, this provision intends to maintain CO2

levels which are within the range that is safe for human occupation.

 

Existing Law or Regulation:

The current edition of the California Energy Code, CCR, Title 24, Part 6, Section 121(c) identifies the sensors, controls and devices required to keep CO2 emissions at safe levels.

 

Compliance Method:

Design Team: The designer should specify and show calculations and locations for CO2 sensors in the construction documents. The team familiar with demand control ventilation will be familiar with these requirements.

 

Contractor: The contractor should install the specified equipment and make sure that it is operating as designed. Again, familiarity with demand control ventilation will be an advantage.

 

Suggestion:

Contractor: Retain product data sheets for onsite verification by the enforcing agency and for the operation and maintenance manual.

 

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans, specifications and calculations to confirm that sensors are included which meet the requirements of Part 6.

 

On-Site Enforcement: The inspector should review the permit set of plans and product data sheets to verify that complying sensors displaying readings are installed in designated locations. He/she should obtain assurance that the readings are recorded as required by Part 6.

 

CALGreen Section: 5.714.7.3 Carbon dioxide (CO2) monitoring. [BSC] For buildings equipped with demand control ventilation, CO2 sensors and ventilation controls shall be specified and installed in accordance with the requirements of 2010 California Energy Code, Section 121(c).

 

Intent:

This section intends to provide clarity to the code user regarding carbon dioxide monitoring systems to protect occupant health and minimize GHG emissions. It is limited to additions and

alterations to buildings equipped with demand control ventilation and as provided in theCalifornia

Energy Code, Part 6, Title 24.

 

Compliance and Enforcement: See § 5.506.2 of this guide

 

 

 

NONRESIDENTIAL, HIGH-RISE RESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS

 

 

 

 

 

NONRESIDENTIAL, HIGH-RISE RESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS

 

 

 

 

 

be  reduced  below  the  level  required  by  Section

121(b)2 for up to 5 minutes each hour if the average rate for each hour is equal to or greater than the required ventilation rate.


B. CO2 sensors shall be located in the room between 3 ft and 6 ft above the floor or at the anticipated height of the occupants heads;

C. Demand  ventilation  controls  shall  maintain  CO

 

Note: VAV must comply with Section 121(c)1 at min- imum supply airflow.

 

2. Pre-occupancy. The lesser of the minimum rate of out- door air required by Section 121(b)2 or three complete air changes shall be supplied to the entire building dur- ing the one-hour period immediately before the build- ing is normally occupied.

 

2

concentrations less than or equal to 600 ppm plus the

outdoor air CO2 concentration in all rooms with CO2

sensors;

Exception to Section 121(c)4C: The outdoor air ventilation rate is not required to be larger than the design outdoor air ventilation rate required by Sec- tion 121(b)2 regardless of CO2  concentration.

 

3. Required demand control ventilation. HVAC sys-


D. Outdoor air CO2


concentration shall be determined

 

tems  with  the  following  characteristics  shall  have

demand ventilation controls complying with Section

121(c)4:

A. They have an air economizer; and


by one of the following:

i.   CO2  concentration shall be assumed to be 400 ppm without any direct measurement; or

ii.  CO2   concentration shall be dynamically mea-

 

B. They serve a space with a design occupant density,


sured using a CO2


sensor located within 4 ft of

 

or a maximum occupant load factor for egress pur-

poses in the CBC, greater than or equal to 25 people per 1000 ft2  (40 square feet per person); and

C. They are either:

i.   Single zone systems with any controls; or

ii.  Multiple zone systems with Direct Digital Con- trols (DDC) to the zone level.

Exception 1 to Section 121(c)3: Classrooms, call centers, office spaces served by multiple zone sys-


the outdoor air intake.

E. When  the  system  is  operating  during  hours  of expected occupancy, the controls shall maintain sys- tem outdoor air ventilation rates no less than the rate listed in Table 121-A times the conditioned floor area for spaces with CO2  sensors, plus the rate required by Section 121(b)2 for other spaces served by the system, or the exhaust air rate, whichever is greater.

F. CO sensors shall be certified by the manufacturer to

 

tems that are continuously occupied during normal


2

be accurate


within plus or minus 75 ppm at a 600 and

 

business hours with occupant density greater than

25 people per 1000 ft2  per Section 121(b)2B, healthcare facilities and medical buildings, and public areas of social services buildings are not required to have demand control ventilation.

Exception 2 to Section 121(c)3: Where space exhaust is greater than the design ventilation rate specified in Section 121(b)2B minus 0.2 cfm per ft2  of conditioned area.

Exception 3 to Section 121(c)3: Spaces that have processes or operations that generate dusts, fumes, mists, vapors or gases and are not provided with local exhaust ventilation, such as indoor operation of internal combustion engines or areas designated for unvented food service preparation, or beauty salons shall not install demand control ventilation.

Exception 4 to Section 121(c)3: Spaces with an area of less than 150 square feet, or a design occu- pancy of less than 10 people per Section 121(b)2B.

4. Demand control ventilation devices.

A. For each system with demand control ventilation, CO2  sensors shall be installed in each room that meets the criteria of Section 121(c)3B with no less than one sensor per 10,000 ft2 of floor space. When a zone or a space is served by more than one sensor, a signal from any sensor indicating that CO2 is near or at the setpoint within a space shall trigger an increase in ventilation to the space;

 

1000 ppm concentration when measured at sea level and 25°C, factory calibrated or calibrated at start-up, and certified by the manufacturer to require calibra- tion no more frequently than once every 5 years. Upon detection of sensor failure, the system shall provide a signal which resets to supply the minimum quantity of outside air to levels required by Section

121(b)(2) to the zone serviced by the sensor at all times that the zone is occupied.

G. The CO2 sensor(s) reading for each zone shall be dis- played continuously, and shall be recorded on sys- tems with DDC to the zone level.

(d) Ducting for zonal heating and cooling units. Where a return plenum is used to distribute outdoor air to a zonal heat- ing or cooling unit, which then supplies the air to a space in order to meet the requirements of Section 121(b)2, the outdoor air shall be ducted to discharge either:

1. Within 5 feet of the unit; or

2. Within 15 feet of the unit, substantially toward the unit, and at a velocity not less than 500 feet per minute.

(e) Design and control requirements for quantities of outdoor air. All mechanical ventilation and space-condition- ing systems shall be designed with and have installed ductwork, dampers and controls to allow outside air rates to be operated at the larger of (1) the minimum levels specified in Section 121(b)1; or (2) the rate required for make-up of exhaust systems that are required for a process, for control of odors, or for the removal of contaminants within the space.