CalGreen July 2012- Non Residential: 5.507.4 Acoustical control

 Comments Off on CalGreen July 2012- Non Residential: 5.507.4 Acoustical control
Dec 092012
 

5.507.4 Acoustical control

STC : Sound transmission class

‐ OITC : Outdoor‐indoor sound transmission class

– CNEL : Community noise equivalent level

‐    Distance to airports and freeways are removed

‐ Envelope: STC 50 or OITC 40, Windows: STC 40 as 30) or OITC 30 for:

o  Within 65 CNEL noise contour of an airport

o Within 65 CNEL or Ldb noise contour of a freeway, expressway, railroad, industrial or other sources determined by the General Plan

‐ Buildings exposed to 65 dB where noise contours are not available:

o Envelope: STC 45 or OITC 35,

Windows: STC 40 or OITC 30 ‐ Performance method: provide interior noise environment not exceeding 50 dBA

 

SECTION 5.507 ENVIRONMENTAL COMFORT

 

CALGreen Section: 5.507.4 Acoustical control. Employ building assemblies and components with Sound Transmission Class (STC) values determined in accordance with ASTM E90 and ASTM E413 or Outdoor-Indoor Sound Transmission Class (OITC) determined in accordance with ASTM E1332, using either the prescriptive or performance method in Section 5.507.4.1 or

5.507.4.2.

 

Exception:  Buildings with few or no occupants or where occupants are not likely to be affected by exterior noise, as determined by the enforcement authority, such as factories, stadiums, storage, enclosed parking structures, and utility buildings.

 

5.507.4.1 Exterior noise transmission, prescriptive method. Wall and roof-ceiling assemblies exposed to the noise source making up the building envelope shall meet a composite STC rating of at least 50 or a composite OITC rating of no less than 40, with exterior windows of a minimum STC of 40 or OITC of 30 in the following locations:

 

1. Within the 65 CNEL noise contour of an airport

 

Exceptions:

1. Ldn or CNEL for military airports shall be determined by the facility Air Installation

Compatible Land Use Zone (AICUZ) plan.

2. Ldn or CNEL for other airports and heliports for which a land use plan has not been developed shall be determined by the local general plan noise element.

 

2. Within the 65 CNEL or Ldn noise contour of a freeway or expressway, railroad, industrial source or fixed-guideway noise source as determined by the Noise Element of the General Plan

 

5.507.4.1.1 Noise exposure where noise contours are not readily available. Buildings exposed to a noise level of 65 dB Leq-1-hr during any hour of operation shall have exterior wall and roof-ceiling assemblies exposed to the noise source meeting a composite STC rating of at least 45 (or OITC 35), with exterior windows of a minimum STC of 40 (or OITC

30).

 

5.507.4.2 Performance method. For buildings located as defined in Sections A5.507.4.1 or A5.507.4.1.1, wall and roof-ceiling assemblies exposed to the noise source making up the building envelope shall be constructed to provide an interior noise environment attributable to exterior sources that does not exceed an hourly equivalent noise level (Leq-1Hr) of 50 dBA in occupied areas during any hour of operation.

 

5.507.4.2.1 Site features. Exterior features such as sound walls or earth berms may be utilized as appropriate to the project to mitigate sound migration to the interior.

 

5.507.4.2.2 Documentation of compliance. An acoustical analysis documenting complying interior sound levels shall be prepared by personnel approved by the architect or engineer of record.

 

5.507.4.3 Interior sound transmission. Wall and floor-ceiling assemblies separating tenant spaces and tenant spaces and public places shall have an STC of at least 40.

 

Note:  Examples of assemblies and their various STC ratings may be found at theCalifornia

Office of Noise Control: http://www.toolbase.org/PDF/CaseStudies/stc_icc_ratings.pdf .

 

Intent:

Where buildings are sited in the noisy areas described in this provision, the intent is to keep sound levels low enough to carry out the activities that take place inside the building without the distraction or discomfort of unwanted noise.

 

Change for 2012: This section is proposed for modification in response to comment to include performance and prescriptive measures to achieve compliance with exterior noise transmission, using measurements recognized in acoustical industry practice. It coordinates noise exposure locations with those cited in local general plans and aligns also with Chapter 12 of the California Building Code for noise control in residential occupancies regulated by HCD.

 

Existing Law or Regulation:

There is NO current law or regulation for this code provision for nonresidential buildings. There may be local ordinances that apply in those communities that have noise exposure such as

commercial airports.

 

Compliance Method:

Design Team: The designer should determine if a building’s location requires compliance, then specify and detail wall and ceiling assemblies and show in the construction documents, show on

plans and/or sections the placement of sound walls and floor/ceilings.

 

Contractor: The contractor should install the wall and ceiling assemblies as designed.

 

Suggestion:

Employing the services of an acoustical engineer is another option to assist with compliance and is required if using the performance method.  Choose an assembly from the “examples of assemblies” link that meet the corresponding sound ratings class.

 

Note: Examples of assemblies and their various STC ratings may be found at:

http://www.toolbase.org/PDF/CaseStudies/stc_icc_ratings.pdf .

 

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans, specifications and calculations to confirm that STC ratings are included which meet the requirements of this section.

 

On-Site Enforcement: The inspector should review the permit set of plans and product data sheets to verify that complying wall and ceiling assemblies are installed correctly.

CALGreen Section: 5.714.7.4.1  Acoustical control. Employ building assemblies and components with Sound Transmission Class (STC) values determined in accordance with ASTM E90 and ASTM E413 or Outdoor-Indoor Sound Transmission Class (OITC) determined in accordance with ASTM E1332 using either the prescriptive or performance method in Section 5.714.1.1 or 5.714.1.2.

 

Exception:  Buildings with few or no occupants or where occupants are not likely to be affected by exterior noise, as determined by the enforcement authority, such as factories, stadiums, storage, enclosed parking structures, and utility buildings.

 

5.714.7.4.2 Exterior noise transmission, prescriptive method. Wall and roof-ceiling assemblies exposed to the noise source making up the building addition or altered envelope shall meet a composite STC rating of at least 50 or a composite OITC rating of no less than 40, with exterior windows of a minimum STC of 40 or OITC of 30 in the following building locations:

 

1.  Within the 65 CNEL noise contour of an airport

 

Exceptions:

1.  Ldn or CNEL for military airports shall be determined by the facility Air Installation Compatible

Land Use Zone (AICUZ) plan.

2.  Ldn or CNEL for other airports and heliports for which a land use plan has not been developed shall be determined by the local general plan noise element.

 

2.  Within the 65 CNEL or Ldn noise contour of a freeway or expressway, railroad, industrial source or fixed-guideway noise source as determined by the Noise Element of the General Plan

 

5.714.7.4.2.1 Noise exposure where noise contours are not readily available. Buildings exposed to a noise level of 65 dB (Leq-1Hr) during any hour of operation shall have building addition or alteration exterior wall and roof-ceiling assemblies exposed to the noise source meeting a composite STC rating of at least 45 (or OITC 35), with exterior windows of a minimum STC of 40 (or OITC 30).

 

 

5.714.7.4.2.2 Performance method.  For buildings located as defined in Sections A5.714.7.1.1 or A5.714.7.1.1.1, wall and roof-ceiling assemblies exposed to the noise source making up the building addition or altered envelope shall be constructed to provide an interior noise environment

attributable to exterior sources that does not exceed an hourly equivalent noise level (Leq-1Hr) of

50 dBA in occupied areas during any hour of operation.

 

5.714.7.4.2.3 Site features.  Exterior features such as sound walls or earth berms may be utilized as appropriate to the addition or alteration project to mitigate sound migration to the interior.

 

5.714.7.4.2.4 Documentation of compliance.  An acoustical analysis documenting complying interior sound levels shall be prepared by personnel approved by the architect or engineer of record.

 

 

5.714.7.4.3 Interior sound transmission. Wall and floor-ceiling assemblies separating tenant spaces and tenant spaces and public places in additions and in alterations modifying existing partitions or installing new partitions shall have an STC of at least 40.

 

Note:  Examples of assemblies and their various STC ratings may be found at the California Office of

Noise Control:  http://www.toolbase.org/PDF/CaseStudies/stc_icc_ratings.pdf .

 

Intent:

CBSC adopted these sections as modified for new construction to provide clarity to the code user regarding environmental acoustics. When installed as part of an addition or alteration, new

exterior walls and roof-ceiling assemblies in buildings located near specified noise-producing neighbors, as well as new wall and floor-ceiling assemblies separating tenants inside the building,

shall comply. The proposed provisions are intended to have a positive health and psychological

impact on building occupants and promote healthy work attendance and increased productivity.

 

 

Compliance and Enforcement: See § 5.507 of this guide

 

CalGreen July 2012- Residential: Most Importance Changes: List

 Comments Off on CalGreen July 2012- Residential: Most Importance Changes: List
Dec 092012
 

Chapter 4 RESIDENTIAL MANDATORY MEASURES Division 4.3 Water Efficiency and Conservation

4.303.1          Twenty percent  savings.                                          Table 4.303.2      Fixture Fiow Rates

•      Identifies methods used for calculation of water use as the “Prescriptive Method” and “Pertormance Method.”

•      Clarifies that kitchen faucets may temporarily increase flow rate to 2.2 gpm, but must default back to 1.8 gpm.

•      Recognizes  the use of nonresidential  lavatory faucets in residential applications.

 

4.303.2          Multiple showerheads serving  one shower.

•      Clarifies that flow rates apply to individual shower valves regardless of the number of showerheads connected to that valve.

 

Division 4.4 Material Conservation and Resource Efficiency

4.408.1 Construction waste management. 4.408.2 Construction waste management plan.
4.408.3 Waste management company. 4.408.4 Waste stream reduction alternative.

•      Clarifies that compliance with, and submittal of, a construction waste management plan is one of the accepted methods for the

required 50% construction  and demolition  waste reduction.

•      Clarifies that referenced materials are “construction and demolition vvaste” materials and adds “source separated” and “single stream” regarding  on site waste sorting or mixing, respectively.

•      Identifies additional methods for compliance, including a waste stream reduction method of compliance for projects generating

construction  waste of 4 pounds or less per square foot of building area.

•      Provides a reference to revised and newly developed sample Construction  Waste Management  forms to be maintained on

HCD’s website and available for download; and in the CALGreen Guide.

 

Division 4.5 Environmental Quality

4.504.1          Covering  of duct openings and protection of mechanical equipment during  construction.

•      Clarifies application to ventilating equipment and to also reduce the amount of water which may enter the system.

 

4.504.3          Carpet systems.

•      Updates an existing reference to the California Department of Public Health’s (CDPH) “Standard Method for the Testing and Evaluation of Volatile Organic Chemical  Emissions from Indoor Sources Using Environmental Chambers”,  Version 1.1, February 2010 (also known as Specification 01350) for purposes of testing and compliance.

 

4.504.4          Resilient flooring systems.

•      Updates an existing reference to the CDPH’s Specification 01350 (see 4.504.3 above) and provides additional references for purposes of testing and compliance.

 

4.504.5.1       Documentation (for composite wood products)

•      Recognizes  products labeled and invoiced as meeting the California Air Resources Board’s Airborne Toxic Control Measure to

Reduce Formaldehyde Emissions from Composite Wood Products in theCaliforniaCode of Regulations.

•      Recognizes exterior grade products meeting the PS-1 or PS-2 standards of the Engineered Wood Association, the Australian

AS/NZS 2269 or European 636 3S standards.

 

4.505.2          Concrete slab foundations.

•          Identifies that requirements for vapor retarders in both the California Building Code and California Residential Code trigger the capillary break requirements of CALGreen.

CalGreen July 2012- Residential: Construction Documentation & FAQ 3

 Comments Off on CalGreen July 2012- Residential: Construction Documentation & FAQ 3
Dec 092012
 

Construction Documents and Installation Verification

 

CALGreen requires that construction documents and other data be submitted in one or more sets with a permit application.  Documents must provide information in sufficient detail to determine compliance with CALGreen and other codes. CALGreen provides the enforcing agencies discretion to require additional construction documents or to waive construction documents, as specified. CALGreen also provides for use of alternate methods of documentation demonstrating substantial conformance when satisfactory to the enforcing agency.

 

Frequently Asked Questions

 

Q: Are any documents available that compare CALGreen with established third-party rating systems?

 

A: HCD is aware that more than one CALGreen comparison document exists. Those comparison documents may analyze all or just a portion of the CALGreen code. Some of these comparative analyses may be accessed through the Internet and others may be proprietary or internal documents.

 

HCD has been involved in the review and development of some of these documents and has determined that it is not possible to accurately compare the contents of a mandatory code to a voluntary program. HCD expressed this opinion and provided input to the developers of some of these documents; however, HCD cannot endorse the usability or accuracy of the comparative analysis documents that are currently being circulated.

 

Q: The definition of “Residential Building” in Section 202 provides a reference to “low-rise residential building”. “Low-Rise Residential Building” is further defined to include

R occupancy buildings, three stories or less, or a one- or two-family dwelling or townhouse. Does this mean that four story and taller apartment and condominium buildings are classified as nonresidential? Is this the intent of the code?

 

A: No. Residential buildings taller than three stories are not considered low-rise residential buildings by definition, but are still residential occupancies. Only residential buildings three stories or less are covered by the scope of CALGreen (Section 101.3.1, #3). Residential buildings taller than three stories are not nonresidential buildings and do not need to comply with the nonresidential portions of the CALGreen code.

 

Q: How does CALGreen apply to residential buildings which include a parking garage or other use below the residential stories?

 

A: CALGreen applies to low-rise residential structures of three stories or less. In the case of podium or pedestal construction, the number of floors or stories of residential use determine whether CALGreen’s provisions for low-rise residential apply.

 

For example, a five story building with a parking garage on the first level has four stories of residential construction above it. CALGreen’s provisions for low-rise residential would not apply to the residential construction since there are more than three stories of residential use involved.

 

Q: Does CALGreen apply to attached or detached garages?

 

A: The residential provisions of CALGreen apply to low-rise residential structures in Occupancy Group R (Residential Group R). Private garages, unless exceeding size or other specified limits, are U occupancies pursuant to the California Building Code. Parking garages are in Storage Group S-2 and, therefore, exempt from the CALGreen code.

 

However, in the case of attached garages, it may be impractical to separately address building standards for the main low-rise residential structure and an attached garage. For example, it would be impractical to plan for retention of storm water, track construction waste, or save topsoil from only the residential portions of the project.

 

Local enforcing agencies may choose to specify or clarify if attached and/or detached garages associated with residential uses also would be subject to green building standards. This would constitute a local amendment more restrictive than the statewide CALGreen provisions and require a local ordinance adoption process, findings, and filing with the California Building Standards Commission.

 

Q: Section 102.3 of CALGreen is titled “Verification”, which requires that “Documentation of conformance for applicable green building measures be provided to the enforcing agency”. What type of documentation, and by whom, will meet the provisions of this section?

 

A: The documentation must be sufficient to satisfy Section 703.1 and the enforcing agency.

 

Q: If a local agency already has a green building ordinance, will it get “grandfathered” in when the 2010 CALGreen Code becomes effective? If not, how does the local ordinance retain its enforceability?

 

A: CALGreen standards do not necessarily replace existing local green building ordinances; however, CALGreen does include provisions that are mandated on a statewide basis. Every local agency is required to enforce the mandatory provisions of CALGreen and cannot replace it with a locally adopted green building ordinance. In cases where a local green building ordinance exists, the provisions in the local ordinance need to be equivalent to, or more restrictive than, requirements in CALGreen. These ordinances need to be updated to reflect CALGreen and the other new codes that are effective on January 1, 2011, and approved

statewide amendments to these codes. In addition, an adopted local ordinance and supporting findings are required to be filed with the California Building Standards Commission to be enforceable.

 

Q: Can a local jurisdiction adopt building standards, including “green building standards”, which are more stringent than those adopted by the State?

 

A: Yes. Health and Safety Code Sections 17958.5 and 18941.5 were amended by Assembly

Bill 210 (Hayashi, Chapter 89, Statutes of 2009) to clarify this issue. Health and Safety Code Section 17958.5 provides for cities, counties, and cities and counties to make changes or modifications to building standards, including green building standards, due to local climatic, geological or topographical conditions. Section 18941.5 clarifies that Building Standards Law cannot limit local establishment of more restrictive building standards, including green building standards, reasonably necessary due to local climatic, geological or topographical conditions. The local jurisdiction must follow procedural requirements, including making of findings, to formally adopt building standard modifications.

 

Q: Can a local jurisdiction expand the applicability of Chapters 4 and A4 to all Group R

occupancies taller than three stories?

 

A: Yes; however, compliance with Section 101.7 is required.

 

Q: Can local jurisdictions apply local amendments retroactively?

 

A: No. Health and Safety Code Sections 17912 and 18398.5 (a) and (b) require that only building standards effective at the local level at the time of permit application apply to the plans and specifications and construction performed under that permit. Similarly, additions or modifications to the California Building Standards Code (residential occupancies) apply only to building permit applications submitted after the effective date of the local ordinance.

 

Q: When adopting local amendments, do the local climatic, geological or topographical conditions have to be unique to that local jurisdiction?

 

A: No. There are several Attorney General Opinions and related court findings that make it clear the local jurisdictions have a great deal of latitude in making the determination of what constitutes “local climatic, geological or topographical conditions.” The Attorney General has indicated that “lacking specific statutory limitations, the local jurisdiction maintains great latitude in determining what constitutes an appropriate local climatic, geological or topographical condition.”

 

Q: Is it true that “environmental” justification is now allowed in addition to the local conditions of climatic, geographical and topographical justification?

 

A: Yes. CALGreen Section 101.7.1 allows consideration of environmental conditions when adopting local amendments.

 

Q: How would a jurisdiction use the “environmental” justification and does it differ from a climatic justification?

 

A: The environmental justification would be used similar to how ordinances are enacted. This allows local cities and counties to address their specific needs. The environmental justification is based on the local environment and its needs, and used in conjunction with climatic, geological or topographical conditions.

 

Q: Are there any limitations or restrictions that apply to adoption of local ordinances related to green building standards? (Also see the next question regarding local modifications related to energy efficiency building standards.)

 

A: Yes. There are several (administrative) limitations.

 

> According to state law, the local jurisdiction shall make express findings that amendments are reasonably necessary due to local conditions. The findings shall be made available as a public record. An ordinance must be adopted using the established proceedings and processes of

the local government.

 

> The local jurisdiction cannot begin to enforce their local modifications to CALGreen until the ordinance and the local finding have been formally filed with the California Building Standards Commission (CBSC). The CBSC serves as a central filing point or statewide database for

local amendments. Although the CBSC does not review local amendments for adequacy, they may reject a local amendment if not supported by findings.

 

> Local ordinances apply to the version of the code as specified in the local ordinance and applicable findings. Local ordinances need to be re-filed to ensure or maintain applicability to new versions of the building standards code especially since adopted model code references may differ substantially through reorganization and updating.

 

> Additional information on local amendments is available in CALGreen Section 101.7, Health and Safety Code Section 17958.7, and on the CBSC website addressing local amendments (www.bsc.ca.gov).  The CBSC has also published information bulletins to address local amendments to the California Building Standards Code and CALGreen.

 

Q: Are there any special administrative requirements that apply if the local modification includes revisions to the energy efficiency standards adopted by the California Energy Commission?

 

A: Yes. The local jurisdiction is required to make a determination that the local energy ordinance is cost effective and at least as stringent as the state energy standards. The “cost effectiveness determination”, stringency analysis, and the local ordinance must be adopted using the local public ordinance adoption process allowing for public review and comment. Local energy ordinances must be approved by the California Energy Commission and filed with the California Building Standards Commission. Further information on this process is

available on the California Energy Commission website (www.energy.ca.gov) addressing local ordinances exceeding the 2010 California Energy Code.

CalGreen July 2012- Residential: 4.106.3. Grading and paving.

 Comments Off on CalGreen July 2012- Residential: 4.106.3. Grading and paving.
Dec 092012
 

4.106.3. Grading and paving. Construction plans shall indicate how the site grading or drainage system will manage all surface water flows to keep water from entering buildings.  Examples of methods to manage surface water include, but are not limited to, the following:

 

1.     Swales

2.     Water collection and disposal systems

3.     French drains

4.     Water retention gardens

5.     Other water measures which keep surface water away from buildings and aid in groundwater recharge.

 

COMMENTARY

 

Purpose:

This section provides protection from unintended entry of surface water and requires construction plans to show how surface water will be managed. Site design and proper installation of drainage systems will help builders protect structures from the dangers of flooding or subsurface water infiltration. This is especially important in areas where setbacks or obstacles interfere with proper surface drainage.

 

Examples of Acceptable Methods of Implementation and/or Compliance:

•      Develop and implement control methods to address ground water flow both above and below the surface to ensure water flow away from the building.

•      Channel rain gutter discharge away from the building during large or intense rain events.

Builders should consider site design mimicking water flows similar to the natural environment.

•      Additional design strategies that can be considered are:

 

Ø     Sloped ground surfaces

Ø     Properly placed drains

 

Background:

During large rain events the ground can become saturated causing runoff and/or ponding in low- lying areas, which can cause water to migrate into buildings. It is critically important to channel rain gutter discharge away from the building during these events. Builders should consider site design that mimics water flows similar to the natural environment and incorporate methods as described in this section.

 

In order to keep a site well-drained and stable, designers and contractors should consider both storm water from the roof and rainwater penetrating into the area around the site. Ground water can flow above or below the surface. Control methods should be developed and implemented which allow for both types of ground water flow to ensure water can continually flow away from the building.

 

Frequently Asked Questions

Q: Do local storm water ordinances need findings and filing?

 

A: Sometimes. It is best to check with a specific local municipality about the local ordinance adoption process and required resolutions, findings and filings. Local charters typically address procedures for adopting, amending and rescinding ordinances. Ordinances typically require or prohibit certain actions under specified circumstances and include statements of intent, findings, specific actions required or prohibited, and an adoption clause. Approved ordinances are subsequently incorporated into the county or city codes.

 

The State Water Resources Control Board (SWRCB), Municipal Storm Water Permitting Program, regulates storm water discharges from municipal separate storm sewer systems (MS4s). Although not a formal finding, changes in local ordinances helpful to or enhancing the local storm water program will need to be reported in the local agency’s annual report to the SWRCB.

 

Q: CALGreen Section 4.106.2 requires storm water drainage and retention during construction. Does this requirement apply year-round even though construction will occur during non-rainy season months?

 

A: No. This section provides three methods for complying with this section. The third method involves compliance with a local lawfully enacted storm water management ordinance. In addition, the local enforcing agency has discretion to determine whether these measures are needed based on the potential for storm water impacts during the construction period of the project. However, if there is potential for construction to be postponed or to be extended beyond the initial planned construction phase, the local enforcing agency may consider requirements for storm water drainage and retention as permit requirements for the project.

CalGreen July 2012 – Residential: 4.303.1 Twenty percent Water savings.

 Comments Off on CalGreen July 2012 – Residential: 4.303.1 Twenty percent Water savings.
Dec 092012
 

4.303.1 Twenty percent savings. A schedule of plumbing fixtures and fixture fittings that will reduce the overall use of potable water within the building by at least 20 percent shall be provided. The reduction shall be based on the maximum allowable water use per plumbing fixture and fitting as required by the California Building Standards Code. The 20 percent reduction in potable water use shall be demonstrated by one of the following methods:

 

1.     Prescriptive Method. Each plumbing fixture and fitting shall not exceed the Maximum Flow Rate

at ≥ 20 Percent Reduction column in Table 4.303.2; or

 

2.     Performance Method. A calculation demonstrating a 20 percent reduction in the building “water use” baseline as established in Table 4.303.1 shall be provided. For low-rise residential occupancies, the calculation shall be limited to the following plumbing fixture and fitting types: showerheads, lavatory faucets, water closets and urinals.

 

COMMENTARY

 

Purpose:

This provision helps reduce indoor potable water use. Reduction of water use also results in decreasing the amount of energy needed to transport, process and treat water, thereby contributing to reduction of greenhouse gas emissions.

 

Section 4.303 provides guidelines on how to achieve a 20 percent reduction in indoor water use. There are two options to use for compliance: the prescriptive method and the performance method.

 

The following graphic shows the typical breakdown of indoor water use. As shown, toilets, showers, clothes washers, and faucets are the greatest indoor water users. CALGreen focuses on water use related to toilets (water closets and urinals), faucets and showers for purposes of potable water conservation

CalGreen July 2012 – Residential: 4.303.2 Multiple showerheads serving one shower

 Comments Off on CalGreen July 2012 – Residential: 4.303.2 Multiple showerheads serving one shower
Dec 092012
 

4.303.2 Multiple showerheads serving one shower. When a shower is served by more than one showerhead, the combined flow rate of all the showerheads controlled by a single valve shall not exceed the Maximum Flow Rates at ≥ 20 Percent Reduction column in Table 4.303.2 or the shower shall be designed to only allow one showerhead to be in operation at a time.

 

Exception: The maximum flow rate for showerheads when using the performance method specified in

Section 4.303.1, Item 2, is 2.5 gpm @ 80 psi.

 

COMMENTARY

 

The maximum flow rate established in Table 4.303.2, Maximum Flow Rate at ≥ 20 Percent Reduction column, also covers applications where one or more valves supply multiple showerheads in a single shower enclosure or space. “Fixture types” or sources of water flow include but are not limited to showerheads, handshowers and bodysprayers.

 

The maximum flow rate provisions apply to the total amount of water flow resulting from each valve supplying the individual shower enclosure regardless of the number of attached showerheads (or similar fixtures). For example, if only one water line or valve supplies a shower enclosure or space, the maximum amount of resulting water flow, regardless of the number of showerheads, is 2 gpm @ 80 psi. If two separate valves provide water to separate showerheads, the maximum flow for each valve would be 2 gpm @ 80 psi. If the operation of two showerheads, controlled by one valve, results in more than 2 gpm @ 80 psi total water flow, then only one showerhead may operate at one time.

 

An exception to Section 4.303.2 provides for the maximum water flow rate, as allowed by the California Plumbing Code, to be at 2.5 gpm @ 80 psi. However, this flow rate is only allowed when using the “performance method” for 20 percent reduction for indoor water use.

 

 

4.303.3 Plumbing fixtures and fittings. Plumbing fixtures (water closets and urinals) and fittings (faucets and showerheads) shall meet the standards referenced in Table 4.303.3.

 

COMMENTARY

 

Purpose:

This section provides specifications for plumbing fixtures and fittings referencing the US Environmental Protection Agency’s WaterSense label, for fixture types that could be used to meet the 20 percent reduction criteria.

CalGreen July 2012 – Residential: 4.406.1 Rodent proofing.

 Comments Off on CalGreen July 2012 – Residential: 4.406.1 Rodent proofing.
Dec 092012
 

4.406.1 Rodent proofing. Annular spaces around pipes, electric cables, conduits, or other openings in plates at exterior walls shall be protected against the passage of rodents by closing such openings with cement mortar, concrete masonry or similar method acceptable to the enforcing agency.

 

COMMENTARY

 

Purpose:

This section requires barriers in exterior openings to prevent rodents from entering the dwelling and causing health hazards and/or damage to a building’s components and systems. It addresses the sealing of openings for controlling rodent intrusion, which differs from California Energy Code provisions intended to prevent air leakage.

 

Examples of Acceptable Methods of Implementation and/or Compliance:

Openings should be sealed or closed with materials that cannot be damaged or penetrated by rodents:

 

•      Cement mortar.

•      Concrete masonry.

•      Lightweight concrete/cellular concrete.

•      Similar methods withstanding rodent penetration and approved by the enforcing agency.

 

Background:

The California Energy Code requires joints and other openings in the building envelope, which are potential sources of air leakage, to be sealed to limit infiltration and exfiltration. CALGreen specifically addresses protection of structures from rodent entry, disease and damage. The perceived reference to California Energy Code provisions has been deleted from CALGreen due to redundancy.

 

Rodents can cause significant damage to a building’s structure or operating systems by gnawing on wood, plastic, copper, electrical conduits or other components. They may also damage stored items or personal property. Rats can burrow under building slabs undermining a foundation. A rodent also may nest in insulation and contribute to salmonellosis (food poisoning) and carry

other diseases.

 

Therefore, penetrations, voids, joints and openings in structures need to be sealed to prevent passage of rodents. Openings include, but are not limited to, cuts, holes, and notches in bottom plates, exterior wall openings around plumbing pipes, flues, exhaust vents, and HVAC conduits. Openings as small as ¼ inch can be used by a rodent to enter a wall, crawl space or attic. In addition, doors, windows, or screens should fit tightly. Other openings such as chimneys and vents should be rodentproof without compromising their function. Dense vegetation, especially around roofs, walls and foundations, should be avoided to decrease rodent habitat and access into or onto buildings.

CalGreen July 2012 – Residential: 4.408.1 Construction waste management.

 Comments Off on CalGreen July 2012 – Residential: 4.408.1 Construction waste management.
Dec 092012
 

4.408.1 Construction waste management. Recycle and/or salvage for reuse a minimum of 50 percent of the nonhazardous construction and demolition waste in accordance with either Section 4.408.2, 4.408.3 or

4.408.4, or meet a more stringent local construction and demolition waste management ordinance.

 

Exceptions:

1.     Excavated soil and land-clearing debris.

2.     Alternate waste reduction methods developed by working with local agencies if diversion or recycle facilities capable of compliance with this item do not exist or are not located reasonably close to the

jobsite.

3.     The enforcing agency may make exceptions to the requirements of this section when isolated jobsites are located in areas beyond the haul boundaries of the diversion facility.

 

COMMENTARY

 

Purpose:

Construction waste diverted from landfills will help reduce landfill production of methane gas, a direct greenhouse gas. In addition, reusing and recycling materials typically results in less energy use than producing materials from virgin materials; conservation of the original resources and reduces the burden on landfills.

 

Background:

Where a local jurisdiction has not adopted a greater than 50 percent waste reduction requirement, the mandatory 50 percent waste reduction established in Section 4.408.1 applies. Section 4.408 also provides choices for meeting the waste reduction requirement including alternate waste reduction methods developed in consultation with local agencies. An exception also recognizes that waste facilities may not exist, or be reasonably close to the jobsite, making compliance with the literal requirements and the benefits intended by this section unfeasible. Determination of “reasonably close” will vary by jurisdiction according to the location of a jobsite and the nearest waste/diversion facility or whether the type of waste in question is accepted at the facility. In addition, construction waste reduction, disposal and recycling services may be economically impracticable or unavailable in some areas.

 

Local agencies can employ the use of a variety of strategies; through public and private sector recycling facilities to achieve state mandated waste reduction and recycling goals. Local agencies should be contacted prior to construction to obtain a list of approved waste haulers. The Department of Resources Recycling and Recovery (CalRecycle) also maintains a C & D (construction and demolition) Recyclers Database listing recycling facilities. Any successful recycling program will involve upfront due diligence, planning and the consideration of several factors. Many of these factors include, but are not limited to:

 

•      Local authority approved waste hauler

•      Consideration of distance from the site to the recycling facility

•      Method of recycling: on-site sorting (source separation) or bulk mixed (single stream)

•      Recyclers with a reliable/verifiable performance record

•      Clearly marked bins

•      Routinely checked bins for material accuracy

•      All involved parties are on board/buy-in

•      Load Tags” or “Trip Tickets” are collected and recorded

 

Definitions for “Hazardous waste,” “Recycle or Recycling,” and “Re-use” are located in CALGreen Chapter 2, Section 202. Section 4.408 also supports legal requirements for local jurisdictions to divert 50 percent of solid waste through source reduction, recycling, and composting activities as required in Public Resources Code Section 41780.

 

 

The regulatory text for this section was amended in July 2011 and is effective July 1, 2012

 

4.408.2 Construction waste management plan. Submit a construction waste management plan in conformance with Items 1 through 5. The construction waste management plan shall be updated as necessary and shall be available during construction for examination by the enforcing agency.

 

1.     Identify the construction and demolition waste materials to be diverted from disposal by recycling, reuse on the project or salvage for future use or sale.

2.     Specify if construction and demolition waste materials will be sorted on-site (source-separated) or bulk mixed (single stream).

3.     Identify diversion facilities where the construction and demolition waste material will be taken.

4.     Identify construction methods employed to reduce the amount of construction and demolition waste generated.

5.     Specify that the amount of construction and demolition waste materials diverted shall be calculated by

weight or volume, but not by both.

 

4.408.3 Waste management company. Utilize a waste management company, approved by the enforcing agency, which can provide verifiable documentation that the percentage of construction and demolition waste material diverted from the landfill complies with Section 4.408.1.

 

Note: The owner or contractor may make the determination if the construction and demolition waste materials will be diverted by a waste management company.

 

4.408.4 Waste stream reduction alternative. Projects that generate a total combined weight of construction and demolition waste disposed of in landfills, which do not exceed four (4) lbs./sq. ft. of the building area shall meet the minimum 50 percent construction waste reduction requirement in

Section 4.408.1.

 

 

The regulatory text for this section was amended in July 2011 and is effective July 1, 2012

 

4.408.5 Documentation. Documentation shall be provided to the enforcing agency which demonstrates compliance with Section 4.408.2, Items 1 through 5, Section 4.408.3 or Section 4.408.4.

 

Notes:

1.     Sample forms found in “A Guide to the California Green Building Standards Code (Low-Rise Residential)” located at www.hcd.ca.gov/CALGreen.html may be used to assist in documenting compliance with this section.

2.     Mixed construction and demolition debris (C&D) processors can be located at the California Department of Resources Recycling and Recovery (CalRecycle).

 

COMMENTARY

 

Purpose:

Sections 4.408.2, 4.408.3 and 4.408.4 address approved methods for ensuring compliance with the 50 percent construction and demolition waste requirement of Section 4.408.1. These methods are intended to save raw materials and preserve landfill space, especially where local regulations do not apply or do not meet the required CALGreen 50 percent or greater construction waste diversion rate.

 

Examples of Acceptable Methods of Implementation and/or Compliance:

•      Comply with a local waste management ordinance.

•      Develop and submit a construction waste management plan (CWMP) for approval of the local enforcing agency.

•      Transport all construction waste to a recycling facility having a 50 percent or greater diversion rate.

•      Generate a total combined weight of construction and demolition waste disposed in landfills not to exceed 4 pounds per square foot of the building area.

•      Demonstrate evidence of compliance, through worksheets or haul tags, scales/weight certification from a waste management facility and or/any other records as required by the

enforcing agency.

•      If the project is located outside the haul boundaries of a diversion facility, contact the local authority as soon as possible for resolution. It is recommended that the owner or authorized agent research and discuss all logistical requirements with the enforcing agency early in the plan submittal process.

 

To reduce time and costs of completing a CWMP and/or other compliance documents, optional sample plans and worksheets, that may be used to show compliance with the waste diversion requirements, are available online by clicking on the CALGreen logo in the carousel on the HCD website home page at (http://www.hcd.ca.gov) or by using the hyperlinks in Chapter 8 of this guide. Local enforcing agencies may require completion of additional documents or additional information. Contact the local authority early to discuss and to ensure compliance.

 

Background:

The following discussions provide information on three methods for calculating and documenting construction waste diversion.

 

Compliance Methods and Supporting Documentation

 

The 2010 CALGreen Code, Section 4.408.1 mandates a 50 percent reduction of construction and demolition (C & D) waste from newly constructed low-rise residential projects. During the

planning stage of any new construction project, contact the local jurisdiction and review any local ordinances pertaining to the reduction of construction waste. If a local jurisdiction does not  have a construction waste management ordinance providing for 50 percent or greater reduction in

construction waste contact the local enforcing agency to determine an acceptable compliance method.

 

CALGreen, Section 4.408, recognizes several methods of compliance to meet 50 percent reduction of construction and demolition waste. In addition, HCD developed several options to assist with calculation of construction waste diversion. Whichever method is chosen, it should be supported by waste tracking documentation and shall be made available to the local enforcement agency. (See sample Construction Waste Management Forms and instructions on HCD’s website which may be used for providing documentation of construction waste diversion and compliance with CALGreen; hyperlinks to these documents are provided in Chapter 8.)

 

Construction Waste Management Plan (CWMP). The CWMP option provides a direct and clearly understood route to the successful diversion target of minimizing or reducing the amount

of waste being sent to landfills. With proper planning, on-site posting and awareness, employees and subcontractors will be able to understand and participate in the process. The CWMP should identify materials to be recycled or reused and the method of their disposal as specified in CALGreen Section 4.408.2. The CWMP must also be supported by verifiable documentation that the established diversion goals requirements have been satisfied.

 

A CWMP should be submitted to the local enforcing agency for approval prior to the commencement of construction. Before choosing a tracking method, review of Appendix A4 “Residential Voluntary Measures” in the 2010 CALGreen Code for additional conservation methods to reduce construction waste generation is strongly encouraged.

 

Recycling Facility or Waste Management Company Method. Use of this option requires all construction waste generated by a construction project to be transported to a recycling facility or waste management company that has a waste diversion rate of 50 percent or more. A recycling facility sorts the construction waste it receives and reclaims and recycles 50 percent or more of all the materials. Some larger municipalities have programs to certify their recycling facilities, via audits, as having a diversion rate of 50 percent or greater. Where such a program exists, this method may be the easiest path to achieving compliance. Similar to the volume or weight

method or 4 pounds per square foot method, load tickets, receipts, and facility certification documents indicating the diversion rate for the project should be retained and provided to the local enforcing agency to demonstrate compliance with the 50 percent construction waste reduction requirements of CALGreen. Check with the local enforcing agency for specific requirements.

 

4 Pounds per Square Foot Method or Waste Stream Reduction Alternative. The total waste generated on an average home in California is 8.5 pounds per square foot. The 4 pounds per square foot net waste limit can be achieved through efficient design, careful and accurate material ordering, handling and storage, panelized/pre-fabricated construction, and recycling and reuse. This method considers the construction waste generated at the construction site and not at the manufacturing site where some larger building components may have been precut or preassembled.

 

Similar to the Volume or Weight Documentation Method discussed below, the facility where construction waste is transported will furnish tickets or receipts, which together with the completed Construction Waste Management Worksheets (4 Lbs. per Sq. Ft.) should be retained and provided to the local enforcing agency to demonstrate compliance with the construction waste reduction provisions of CALGreen.

 

Volume or Weight Documentation Method. The waste can be site-sorted (source separated), bulk mixed (single stream), or both. When using this method, documentation and tracking of the volume or weight (not both) of all waste generated by the project and transported to a facility is required. Most facilities will supply tickets or other detailed receipts showing the weight or volume of all materials being recycled, reused, or disposed, which should be retained and provided to the local enforcing agency to demonstrate compliance with CALGreen. Additionally, the weight or volume totals from these tickets or receipts should be entered on the Construction Waste Management Worksheets (Volume or Weight) to verify compliance with CALGreen’s 50 percent waste reduction requirement.

 

Other Documentation Methods

Additional documentation methods for verifying compliance with CALGreen’s construction waste reduction requirements may be used. For example, web-based construction waste management systems may be available which track the history and volume of construction waste generated on a project-by-project basis. All documentation methods used must be acceptable to the local enforcing agency.

CaGreen July 2012 – Residential: FAQ 2

 Comments Off on CaGreen July 2012 – Residential: FAQ 2
Dec 092012
 

Frequently Asked Questions

 

Q: Section 4.406.1 applies to openings at exterior walls. Does this apply to a combination of all openings through exterior walls or just the openings in the top and bottom plates?

 

A: This section requires the sealing of openings, e.g., cuts, holes and notches in bottom plates, to prevent entry of rodents and the resulting damage.

 

Q: CALGreen requires that 100 percent of excavated soil and land clearing debris must be reused or recycled for commercial projects. Does this requirement also apply to residential projects?

 

A: No. CALGreen Section 408.1 requires 50 percent reduction of construction waste with a specific exception for excavated soil and land-clearing debris from this requirement. Unlike the provisions for nonresidential construction, there are no mandatory requirements for reuse or recycling of excavated soil and land-clearing debris. However, CALGreen  voluntary Tier 1

level of enhanced green building does include a prerequisite for topsoil protection and reuse (Section A4.106.2.3). As noted, this is not a mandatory requirement of CALGreen unless the voluntary Tier 1 level is adopted or the measure is specifically required at the local level.

 

Q: The building department in my jurisdiction does not allow the reuse of previously used materials. Is reuse of materials a violation of CALGreen?

 

A: No. There are provisions for used materials in the California Building Standards Code. The code specifies that used materials, equipment and devices shall not be reused unless approved by the building official. This means that some materials cannot be reused if they do not comply with the requirements of the California Building Standards Code and/or the local ordinances for new construction. CALGreen Sections A4.105.1 and A4.105.2 state that reused materials or products must comply with current building standards requirements or be an accepted alternate method or material.

 

Q: Is a building operation and maintenance manual required for each condominium, duplex or dwelling unit?

 

A: Yes. Each individually-owned unit in a multifamily building shall have an approved operation and maintenance manual at the time of final inspection. Information must be for the appropriate dwelling unit or building. Paper or electronic copies of these documents are acceptable. The required documentation must stay with the building or dwelling unit throughout its life-cycle and be accessible to the owner, tenant or the individual(s) responsible for operating the feature, equipment or device.

 

Q: Is a building operation and maintenance manual required for each apartment dwelling unit?

 

A: No. In multifamily dwellings not individually-owned, such as an apartment complex, it is not the intent of HCD to require a complete operation and maintenance manual in each individual dwelling unit. An individual operation and maintenance manual may be necessary for each building where dwelling unit features differ within an apartment community or where different special inspections have been required for each building. However, a single comprehensive manual may be permitted when approved by the local enforcing agency.

 

Tenant rights and responsibilities typically vary with each rental contract. The building owner/manager shall retain the original manual(s), which must remain on-site and made available for review by all tenants. All maintenance and operation information for all applicable features of a dwelling unit and common areas shall be provided to whoever is responsible for operating the feature, equipment or device. When the tenant is the responsible party, applicable maintenance or operating information shall be provided to them. Photocopied information from the approved manual is acceptable. Public transportation options or other information required by the manual, applicable to all individual tenants, may be provided individually or at a central location where all tenants have access.

 

Q: Is a building operation and maintenance manual required for each guest room in hotels/motels?

 

A: No. All operation and maintenance information for all applicable features of guest rooms and common areas shall be provided to whoever is responsible for operating the feature, equipment or device. In hotels/motels, where the occupants are primarily transient in nature, guests are not responsible for the maintenance of the property, buildings or rooms; the only responsible party is the building owner and/or the manager. For more details regarding hotels/motels in which occupants are primarily permanent in nature, see the previous question and answer.

CalGreen July 2012- Residential: 4.504.1 Covering of duct openings and protection of mechanical equipment during construction.

 Comments Off on CalGreen July 2012- Residential: 4.504.1 Covering of duct openings and protection of mechanical equipment during construction.
Dec 092012
 

4.504.1 Covering of duct openings and protection of mechanical equipment during construction.  At the time of rough installation, during storage on the construction site and until final startup of the heating, cooling and ventilating equipment, all duct and other related air distribution component openings shall be covered with tape, plastic, sheetmetal or other methods acceptable to the enforcing agency to reduce the amount of water, dust and debris, which may enter the system.

 

COMMENTARY

 

Purpose:

This section provides protection for duct openings, permanent mechanical equipment and other components which are often used for conditioning and ventilating during construction. Protection would result in reduced recirculation of construction dust, debris and other airborne contaminants upon occupancy, reduce moisture and water intrusion, and increase operating efficiency.

 

Examples of Acceptable Methods of Implementation and/or Compliance:

•      Several methods of protection are acceptable ranging from supply boots to cardboard and duct tape to specially designed rolled sheeting. Protection should have sufficient strength and be securely fastened to provide protection during the timeframe needed.

•      Equipment, ducting, and plenums should be protected in a method that the protection is successful during the entire construction process.

•      Equipment stored on the construction site for future installation should be wrapped or protected.

•      It is recommended that the system not be operated when airborne contaminants are present.

However, if the system is operated during construction, then it is recommended that a high

efficiency filter such as a MERV 6 or 8, suitable for system capacity, be used throughout the construction process and the system be protected after each use. If the system is used prior to final start-up, it is recommended that the entire system, including ductwork, furnace and coil, be thoroughly cleaned and inspected to remove any construction-related particles.

•      Consider use of alternate space conditioning systems during construction.

 

Background:

Pollutants caused from construction activities are of major concern as they migrate to the duct systems and air-handling units. Both visible and invisible pollutants can greatly affect indoor air quality when distributed throughout the dwelling by a forced air system. Dust, dirt, and airborne particles can substantially reduce the efficiency and operation of coils and compressors. This practice encourages and provides a method of protection to ensure that the long term mechanical efficiency and occupant health is not adversely affected by construction pollution.