Medical Gas (Med Gas) Systems- International Fire code – Section 2006

 Comments Off on Medical Gas (Med Gas) Systems- International Fire code – Section 2006
Mar 132013
 

The final main code is Uniform Fire Code:

SECTION 3006
MEDICAL GAS SYSTEMS

3006.1 General. Compressed gases at hospitals and similar facilities intended for inhalation or sedation including, but not limited to, analgesia systems for dentistry, podiatry, veterinary and similar uses shall comply with Sections 3006.2 through 3006.4 in addition to other requirements of this chapter.

3006.2 Interior supply location. Medical gases shall be stored in areas dedicated to the storage of such gases without other storage or uses. Where containers of medical gases in quantities greater than the permit amount are located inside buildings, they shall be in a 1-hour exterior room, a 1-hour interior room or a gas cabinet in accordance with Section 3006.2.1, 3006.2.2 or 3006.2.3, respectively. Rooms or areas where medical gases are stored or used in quantities exceeding the maximum allowable quantity per control area as set forth in Section 2703.1 shall be in accordance with the International Building Code for high-hazard Group H occupancies.

3006.2.1 One-hour exterior rooms. A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers with a fire-resistance rating of not less than 1 hour. Openings between the room or enclosure and interior spaces shall be self-closing smoke-and draft-control assemblies having a fire protection rating of not less than 1 hour. Rooms shall have at least one exterior wall that is provided with at least two vents. Each vent shall not be less than 36 square inches (0.023 m2) in area. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling. Rooms shall be provided with at least one automatic sprinkler to provide container cooling in case of fire.

3006.2.2 One-hour interior room. When an exterior wall cannot be provided for the room, automatic sprinklers shall be installed within the room. The room shall be exhausted through a duct to the exterior. Supply and exhaust ducts shall be enclosed in a 1-hour-rated shaft enclosure from the room to the exterior (Fire Wrap?!).. Approved mechanical ventilation shall comply with the California Mechanical Code and be provided at a minimum rate of 1 cubic foot per minute per square foot [0.00508 m3/(s . m2)] of the area of the room. (Where is the Mechanical Plan Checker?!)

3006.2.3 Gas cabinets. Gas cabinets shall be constructed in accordance with Section 2703.8.6 and the following:

  1. The average velocity of ventilation at the face of access ports or windows shall not be less than 200 feet per minute (1.02 m/s) with a minimum of 150 feet per minute (0.76 m/s) at any point of the access port or window.
  2. They shall be connected to an exhaust system.
  3. They shall be internally sprinklered.

3006.3 Exterior supply locations. Oxidizer medical gas systems located on the exterior of a building with quantities greater than the permit amount shall be located in accordance with Section 4004.2.1.

3006.4 Medical gas systems. Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter.

SECTION 3007
COMPRESSED GASES NOT OTHERWISE REGULATED

3007.1 General. Compressed gases in storage or use not regulated by the material-specific provisions of Chapters 6, 31, 35 and 37 through 44, including asphyxiant, irritant and radioactive gases, shall comply with this section in addition to other requirements of this chapter.

3007.2 Ventilation. Indoor storage and use areas and storage buildings shall be provided with mechanical exhaust ventilation or natural ventilation in accordance with the requirements of Section 2704.3 or 2705.1.9. When mechanical ventilation is provided, the systems shall be operational during such time as the building or space is occupied.

 

The issues outstanding are many.

 

Industrial gas piping regulations, controls, the hazardous quantities are not checked by nearly anyone or sparse check at best.

 

This section of the code is like an orphan child that no body wants to adopt. However, the immanent danger here is far greater than extreme harsh check for plumbing fixture counts or many archaic planning or building issues.

 

All organizations must address this carefully and adopt a unified program with multidisciplinary departmental approach.

 

Some of the plan checks by other Cities are attached and are good start for the greater LA/OC basin.

 

Saum

Architectural Registration Exam Structural; Site Planning Design; Programming Planning Practice; Building System

 Comments Off on Architectural Registration Exam Structural; Site Planning Design; Programming Planning Practice; Building System
Jan 292013
 

USC are exam preparation structural spd ppp building systems

The file attached is the one file binder of Structural Systems, Site Planning and Design’ Programming Planning Practice, and Building Systems.

If you observe any error, please let us know through facebook…… “Saum Greenerade”.

CALGreen July 2012 Non-Residential: Mandatory Checklist

 Comments Off on CALGreen July 2012 Non-Residential: Mandatory Checklist
Dec 092012
 

                                                                 MANDATORY REQUIREMENTS CHECKLIST

                                           NON-RESIDENTIAL BUILDINGS AND RESIDENTIAL BUILDINGS 

ITEM

#

CODE SECTION

REQUIREMENT

REFERENCE SHEET (Sheet # or N/A)

COMMENTS

(e.g. note # or detail #)

PLANNING AND DESIGN
1 5.106.1 Storm water pollution prevention plan
2 5.106.4.1 Short-term bicycle parking
3 5.106.4.2 Long-term bicycle parking
4 5.106.5.2 Designated parking
5 5.106.5.3.1 Electric vehicle supply wiring
6 5.106.8 Light pollution reduction
7 5.106.10 Grading and Paving
ENERGY EFFICIENCY
8 5.210.1 ENERGY STAR equipment and appliances
9 5.211.4 Prewiring for future solar
10 5.211.4.1 Off grid prewiring for future solar
WATER EFFICIENCY & CONSERVATION
11 5.303.1.1 Buildings in excess of 50,000 square feet/submeter
12 5.303.1.2 Excess consumption
13 5.303.2 20 Percent Savings
14 5.303.2.1 Multiple showerheads serving one shower
15 5.303.4 Wastewater reduction
17 5.304.1 Water budget
18 5.304.2 Outdoor potable water use
19 5.304.3 Irrigation design
MATERIAL CONSERVATION & RESOURCE EFFICIENCY
20 5.407.1 Weather protection
21 5.407.2.1 Sprinklers
22 5.407.2.2 Roof overhangs and recesses entries
23 Nonabsorbent interior finishes
23 5.408.1 Construction waste diversion
24 5.408.4 Excavated soil and land clearing debris
25 5.410.1 Recycling by occupants
26 5.410.2 Commissioning (> 10,000 sq ft.)
27 5.410.2.1 −    Owner’s Project Requirements (OPR)

 

28 5.410.2.2 −    Basis of Design (BOD)−    Commissioning plan−    Functional performance testing

−    Systems manual

−    Systems operations training

−    Commissioning report

29 5.410.2.3
30 5.410.2.4
31 5.410.2.5.1
32 5.410.2.5.2
33 5.410.2.6
34 5.410.4 Testing, adjusting and balancing (< 10,000 sq ft)
35 5.410.4.2 −    Systems−    Procedures−    HVAC balancing

−    Reporting

−    Operation and maintenance manual

−    Inspections and reports

36 5.410.4.3
37 5.410.4.3.1
38 5.410.4.4
39 5.410.4.5
40 5.410.4.5.1
ENVIRONMENTAL QUALITY
41 5.503.1 Fireplace
42 5.503.1.1 Woodstoves
43 5.504.3 Covering of duct openings and protection of mechanical equipment during construction
44 5.504.4 −    Finish material pollutant control−    Adhesives, sealants, and caulks−    Paints and coatings

−    Aerosol Paints and Coatings

−    Verification

45 5.504.4.1
46 5.504.4.3
47 5.504.4.3.1
48 5.504.4.3.2
49 5.504.4.4 Carpet systems
50 5.504.4.4.1 Carpet cushion
51 5.504.4.5 Composite wood products
52 5.504.4.6 Resilient flooring systems
53 5.504.5.3 Filters
54 5.504.7 Environmental tobacco smoke (ETS) control
55 5.505.1 Indoor moisture control
56 5.506.1 Outside air delivery
57 5.506.2 Carbon dioxide (CO2) monitoring
58 5.507.4 Acoustical control
59 5.507.4.1 Exterior noise transmission for roof
60 Exterior noise transmission for walls
61 Exterior noise transmission for windows
62 5.507.4.2 Interior sound
63 5.508.1 Ozone depletion and global warming reductions
64 5.508.1.1 CFCs
65 5.508.1.2 Halons

 

CALGreen July 2012 Non-Residential: Division 5.7 – Additions and alterations to existing nonresidential buildings

 Comments Off on CALGreen July 2012 Non-Residential: Division 5.7 – Additions and alterations to existing nonresidential buildings
Dec 092012
 

Division 5.7 – Additions and alterations to existing nonresidential buildings

July 1, 2012 : 2,000 sq ft additions, $500,000 alterations

•2013 Code: 1,000 sq ft additions, $200,000 alterations

•New Division 5.7“Additions and alterations to existing nonresidential buildings” (State definitions)

DIVISION 5.7 ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS

This is a new division proposed to include standards for additions and alterations to existing nonresidential buildings. The reason for this proposal is to extend the benefits of reduction in greenhouse gas emissions, water use, and polluting finish products to a larger class of buildings than newly constructed buildings. It is modeled after similar provisions recently adopted locally by the City of Los Angeles for its considerable body of construction projects. It proposes and scopes some of the provisions from Divisions 5.3 through 5.5 for which cost benefit analysis was prepared last cycle for the mandatory code. The provisions are those readily applicable to additions and renovations.

SECTION 5.701 – ADMINISTRATION

CALGreen Section: 5.701.1 Scope. For those occupancies subject to section 103 of this code, the provisions of this division shall apply to the planning, design, operation, construction, use and occupancy of additions to buildings or structures unless otherwise indicated in this code. The provisions of this Division shall only apply to the portions of the building being added or altered within the scope of the permitted work. Compliance for additions and alterations is required on or after the dates shown in Table 5.701

TABLE 5.701

Effective date of compliance Square footage of addition

Permit valuation or

estimated construction cost of alteration

July 1, 2012 2000 $500,000
Effective date of the 2013CaliforniaBuildingStandards Code 1000 $200,000

Notes:

1) The effective date of the 2013 California Building Standards Code is currently projected to be January 1, 2014.

2) This division does not apply to additions and alterations of qualified historical buildings.

Intent: Scope for additions and alterations to existing nonresidential buildings is limited to 2000 s.f. for additions and $500,000 for alterations, with that limit to drop in the next edition of the code. At the request of the Division of the State Architect, this section also includes an exception for qualified historic buildings regulated by that agency.

Existing Law or Regulation:

Building standards generally apply to additions and alterations for which a permit is applied. CALGreen has an exception, applying only to newly constructed buildings, so this division aligns CALGreen with other Parts of Title 24. There may be a more stringent local ordinance in place.

Compliance Method:

Determine if the addition or alteration triggers compliance (see Section 5.701 above and Section 7.502 Definitions) then comply with the specific provisions applicable.

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans, specifications for the areas of additions and construction cost estimates for alterations for to confirm the need for compliance.

On-Site Enforcement: The inspector should review the permit set of plans and product data sheets for compliance with specific provisions, following.

 

 SECTION 5.702 – DEFINITIONS

CALGreen Section: 5.702.1 Definitions. Unless otherwise stated, the following words and terms shall, for the purposes of this code, have the meanings shown in this division. Refer also to definitions in Chapter 2 of this code.

ADDITION. An extension or increase in floor area of an existing building or structure.

ALTERATION OR ALTER. Any construction or renovation to an existing structure other than repair for the purpose of maintenance or addition.

ARB (CARB). TheCalifornia Air Resources Board.

Intent:

Section 5.702.1 Definitions.

CBSC is including definitions of addition and of alteration, which are exclusive of each other, taken from the building Code.

SECTION 5.703 GREEN BUILDING

CALGreen Section: 5.703.1 Scope. Building additions and alterations shall be designed to include the green building measures specified as mandatory in the application checklists for alterations or additions contained in this code.

5.703.2 Phased projects. For shell buildings and others constructed for future tenant improvements, only those code measures relevant to the building components and systems considered to be new construction (or newly constructed) shall apply.

5.703.2.1 Tenant improvements. The provisions of this code shall apply to the initial tenant or occupant improvements to a project and to subsequent tenant improvements subject to Section 5.701.1.

Intent:

Section 5.703.1 Scope.

CBSC is proposing that the mandatory provisions in this division be found in the checklists in the appendix in the code.

Section 5.703.2 Phased projects and 5.703.2.1 Tenant improvements. CBSC is proposing to clarify for the code user the application of the provisions of this division to shell buildings and tenant improvements.

 Shell Building Apply Cal Green >> If first tenant move apply Cal Green  >  Second T.I. >1000 sqft or >$200,000.00 work Cal Green Applies

 

 

 

CALGreen July 2012 Non-Residential: 5.106.10 Grading and Paving

 Comments Off on CALGreen July 2012 Non-Residential: 5.106.10 Grading and Paving
Dec 092012
 

 CALGreen Section: 5.106.10 Grading and Paving.  Construction plans shall indicate how site grading or a drainage system will manage all surface water flows to keep water from entering buildings. Examples of methods to manage surface water include, but are not limited to, the following:

1.   Swales; 2.   Water collection and disposal systems; 3.   French drains; 4.   Water retention gardens;

5.   Other water measures which keep surface water away from buildings and aid in groundwater recharge

Intent:

The intent of this code provision is to ensure that newly constructed project sites are planned and developed to keep surface water from entering the building, to extend the longevity of the exterior building walls, to prevent mold and keep moisture from entering the exterior wall and perimeter slabs.

Change for 2012: This provision is being modified slightly to emphasize means of compliance. Grading and paving plans, typically required by enforcing agencies, will show how this is to be accomplished, and a list of methods for managing flows, aligned with the Department of Housing and Community Development’s (HCD) section, has been added.

Existing Law or Regulation:

There is NO current law or regulation for this code provision. However, there are some code sections in the California Building Code (for example Section 1805.3.4 Foundation elevation) that address sloping grades away from buildings but does not address how all surface water flows will be managed on site.

Compliance Method:

Show on the construction documents (site plan or grading plan) how site grading and/or a drainage system will manage all surface water flows to keep water from entering the building. This is particularly critical on sloped sites.

Suggestion: Show on the grading plan, in addition to draining the water away from the exterior walls, how surface water will be managed on site. Methods include but are not limited to, those now listed in the regulation.

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the grading plan and confirm that there are slopes away from the building and adequate measures to manage surface water flows. In addition, the reviewer should ensure that the plans indicate protection from water intrusion for buildings located on sloped sites or having flood plain requirements.

On-Site Enforcement: The inspector should review the permit set of plans to verify that all grading and/or drainage systems have been installed as specified on the approved plans and specifications.

CALGreen July 2012 Non-Residential: 5.710.6.1 Storm water pollution prevention.

 Comments Off on CALGreen July 2012 Non-Residential: 5.710.6.1 Storm water pollution prevention.
Dec 092012
 

CALGreen Section: 5.710.6.1 Storm water pollution prevention. Additions that disturb soil of less than one acre shall prevent the pollution of stormwater runoff from the construction activities through one or more of the following measures:

5.106.1.1 Local ordinance. Comply with a lawfully enacted stormwater management and/or erosion control ordinance.

5.106.1.2. Best management practices (BMP). Prevent the loss of soil through wind or water erosion by implementing an effective combination of erosion and sediment control and good housekeeping BMP.

1. Soil loss BMP that should be considered for implementation as appropriate for each project include, but are not limited to, the following:

a.    Scheduling construction activity

b.    Preservation of natural features, vegetation and soil

c.    Drainage swales or lined ditches to control stormwater flow

d.    Mulching or hydroseeding to stabilize disturbed soils

e.    Erosion control to protect slopes

f.     Protection of storm drain inlets (gravel bags or catch basin inserts)

g.    Perimeter sediment control (perimeter silt fence, fiber rolls)

h.    Sediment trap or sediment basin to retain sediment on site

i.     Stabilized construction exits

j.     Wind erosion control

k.    Other soil loss BMP acceptable to the enforcing agency

2. Good housekeeping BMP to manage construction equipment, materials, and wastes that should be considered for implementation as appropriate for each project include, but are not limited to, the following:

a.    Material handling and waste management

b.    Building materials stockpile management

c.    Management of washout areas (concrete, paints, stucco, etc.)

d.    Control of vehicle/equipment fueling to contractor’s staging area

e.    Vehicle and equipment cleaning performed off site

f.     Spill prevention and control

g.    Other housekeeping BMP acceptable to the enforcing agency

Intent:

The intent of this section means to prevent pollution from storm water runoff similar to that for new construction, where an addition disturbs less than one acre of soil. It recognizes that a local ordinance may govern, and it adds best management practices that can be used to prevent soil loss. This brings renovation projects in line with new construction projects disturbing similar amounts of soil to prevent soil and sediment from entering receiving waters.

Compliance and Enforcement:

See § 5.106.1 of this guide

CALGreen Section: 5.710.6.1 Storm water pollution prevention. Additions that disturb soil of less than one acre shall prevent the pollution of stormwater runoff from the construction activities through one or more of the following measures:   5.106.1.1 Local ordinance. Comply with a lawfully enacted stormwater management and/or erosion control ordinance.   5.106.1.2. Best management practices (BMP). Prevent the loss of soil through wind or water erosion by implementing an effective combination of erosion and sediment control and good housekeeping BMP.   1. Soil loss BMP that should be considered for implementation as appropriate for each project include, but are not limited to, the following: a.    Scheduling construction activity b.    Preservation of natural features, vegetation and soil c.    Drainage swales or lined ditches to control stormwater flow d.    Mulching or hydroseeding to stabilize disturbed soils e.    Erosion control to protect slopes f.     Protection of storm drain inlets (gravel bags or catch basin inserts) g.    Perimeter sediment control (perimeter silt fence, fiber rolls) h.    Sediment trap or sediment basin to retain sediment on site i.     Stabilized construction exits j.     Wind erosion control k.    Other soil loss BMP acceptable to the enforcing agency   2. Good housekeeping BMP to manage construction equipment, materials, and wastes that should be considered for implementation as appropriate for each project include, but are not limited to, the following: a.    Material handling and waste management b.    Building materials stockpile management c.    Management of washout areas (concrete, paints, stucco, etc.) d.    Control of vehicle/equipment fueling to contractor’s staging area e.    Vehicle and equipment cleaning performed off site f.     Spill prevention and control g.    Other housekeeping BMP acceptable to the enforcing agency

Intent: The intent of this section means to prevent pollution from storm water runoff similar to that for new construction, where an addition disturbs less than one acre of soil. It recognizes that a local ordinance may govern, and it adds best management practices that can be used to prevent soil loss. This brings renovation projects in line with new construction projects disturbing similar amounts of soil to prevent soil and sediment from entering receiving waters.     Compliance and Enforcement: See § 5.106.1 of this guide

CalGreen July 2012 Non-Residential: 5.106.4 Bicycle parking

 Comments Off on CalGreen July 2012 Non-Residential: 5.106.4 Bicycle parking
Dec 092012
 

 

CALGreen Section: 5.106.4 Bicycle parking. Comply with Sections 5.106.4.1 and

5.106.4.2; or meet local ordinance, whichever is stricter.

5.106.4.1 Short-term bicycle parking. If the project is anticipated to generate visitor traffic,

provide permanently anchored bicycle racks within 200 feet of the visitors’ entrance, readily

visible to passers-by, for 5 percent of visitor motorized vehicle parking capacity, with a minimum of one two-bike capacity rack.

 

5.106.4.2 Long-term bicycle parking. For buildings with over 10 tenant-occupants, provide

secure bicycle parking for 5 percent of motorized vehicle parking capacity, with a minimum of one

space. Acceptable parking facilities shall be convenient from the street and may include:

1. Covered, lockable enclosures with permanently anchored racks for bicycles;

2. Lockable bicycle rooms with permanently anchored racks; and

3. Lockable, permanently anchored bicycle lockers.

Note: Additional information on recommended bicycle accommodations may be obtained from  Sacramento Area Bicycle Advocates.

 

Intent:

The intent of this code provision is to ensure that newly constructed projects provide short term and/or long term bicycle parking accommodations to promote the use of bicycles as an

alternate means of transportation in an attempt to reduce greenhouse gas emissions.

 

Change for 2012: The proposed modification deletes, at the request of the University of

California, a reference to theUniversityofCalifornia Policyon Sustainable Practices.

 

Existing Law or Regulation:

There is NO current law or regulation for this code provision. However, there are some jurisdictions that have adopted local ordinances.

 

Compliance Method:

Short-Term Bicycle Parking:

Construction documents (plans & specifications and/or site plan) should reflect the location of the required number of short-term permanently anchored bicycle parking racks for 5 percent of visitor motorized vehicle parking capacity, with a minimum of one two-bike capacity rack.

 

Long-Term Bicycle Parking:

1. Determine which of the three options will be used to comply or identify an alternate method(s).

2. Construction documents (plans & specifications and/or site plan) should reflect the method and location of the required number of long-term secured bicycle parking facilities based on 5 percent of motorized vehicle parking capacity, with a minimum of one space.

 

Note: If the applicant is seeking a parking capacity reduction under §A5.106.6, or the local jurisdiction has a zoning ordinance for reduced parking, use the parking requirements that apply before the reduction is taken or outside any special zone in the calculations. This is to recognize that, with reduced parking capacity, more people are likely to ride bicycles.

 

Suggestion: Provide a calculation table or a note on the plans showing the total number of required short-term spaces by multiplying the anticipated visitor parking spaces by 5 percent and for long-term spaces by multiplying the total vehicular parking required spaces by 5 percent.

Examples:

Short-term: Visitor parking capacity at 42 x 5 percent =2.1 – Provide racks for 3 bicycles. Long-term: Total Vehicular parking capacity at 216 x 5 percent =10.8 –Provide 11 spaces.

If specifying lockers, consider using six two-bicycle lockers.

 

Enforcement:

Plan intake: The reviewer and/or plan checker should review the plans and confirm that the correct number of bicycle parking racks and/or secured areas are included with the drawings

and meet the requirements.

 

On-Site Enforcement: The inspector should review the permit set of plans to verify that all required bicycle parking requirements as shown on the plans have been provided and installed.


CALGreen Section: 5.710.6.2 Bicycle parking. Comply with Sections 5.710.6.2.1 and

5.710.6.2.2; or meet the applicable local ordinance, whichever is stricter.

 

5.710.6.2.1 Short-term bicycle parking. If the project is anticipated to generate visitor traffic and adds 10 or more vehicular parking spaces, provide permanently anchored bicycle racks within 200 feet of the visitors’ entrance, readily visible to passers-by, for 5%

of the additional visitor motorized vehicle parking capacity, with a minimum of one two-bike capacity rack.

 

5.710.6.2.2 Long-term bicycle parking. For buildings with over 10 tenant-occupants that add 10 or more vehicular parking spaces, provide secure bicycle parking for 5% of additional motorized vehicle parking capacity, with a minimum of one space. Acceptable parking facilities shall be convenient from the street and may include:

1.   Covered, lockable enclosures with permanently anchored racks for bicycles;

2.   Lockable bicycle rooms with permanently anchored racks; and

3.   Lockable, permanently anchored bicycle lockers.

 

 

 

Intent:

The Intent of this section and subsections require additional bicycle parking when 10 or more parking spaces are added as part of an addition or alteration project, thus encouraging additional building occupants to use alternate forms of transportation to standard automobiles.

Compliance and Enforcement: See § 5.106.4 of this guide

CalGreen July 2012 Non-Residential: 5.106.5.2 Designated parking.

 Comments Off on CalGreen July 2012 Non-Residential: 5.106.5.2 Designated parking.
Dec 092012
 

CALGreen Section: 5.106.5.2 Designated parking. Provide designated parking for any combination of low-emitting, fuel efficient, and carpool/van pool vehicles as follows:

 

[Table 5.106.5.2 not shown – refer to Code]

 

5.106.5.2.1 Parking stall marking. Paint, in the paint used for stall striping, the following characters such that the lower edge of the last word aligns with the end of the stall striping and is visible beneath a parked vehicle:

 

CLEAN AIR/ VANPOOL/EV

 

Note:  Vehicles bearing Clean Air Vehicle stickers from expired HOV lane programs may be considered eligible for designated parking spaces.

 

Intent:

This code provision is to ensure that newly constructed projects provide designated parking

for clean air vehicles (low-emitting, fuel efficient, and carpool/van pool vehicles) which gives reserved parking to those who drive clean air vehicles. The intent is to promote the use of clean air vehicles in an attempt to conserve natural resources and reduce green house gas

emissions.

Clean Air Resource Board

Change for 2012: 2012 modifications, proposed by CARB, are to delete the definition for a PZEV vehicle, which does not qualify, and change the stall marking designation to read CLEAN AIR/VANPOOL/EV to reflect qualifying vehicles that shall be permitted to park there. Based on comment made at the Green Building Code Advisory Committee (GB CAC), CBSC has worked with ARB to shorten the stall marking language and clarify which vehicles are eligible for the parking.

 

Existing Law or Regulation:

There is NO current law or regulation for this code provision. However, there are some jurisdictions that have adopted ordinances.

 


Compliance Method:

Design Team: Construction documents (site plan) should reflect the location of the required

number of designated parking stalls with the marking “CLEAN AIR/VANPOOL/EV” toward the back of the stall, similar to an accessible symbol, so that the writing can be seen when a clean air vehicle is parked. Lettering should be at least 8 inches high. The parking stalls can be located anywhere on the site without preferential location.

 

Suggestion: The plans should reflect the total number of required vehicular spaces and refer to TABLE 5.106.5.2 to ensure that the correct number of designated parking stalls is being provided. Include all parking spaces in the calculation. As approved by the enforcing

agency, some compact stalls may also be marked for clean air vehicles.

 

Examples:

1.   55 total parking spaces: based on TABLE 5.106.5.2 – Provide 6 clean air/vanpool/ev spaces which fall within the range.

2.   240 total parking spaces: based on TABLE 5.106.5.2, calculate 240 x 8 percent =

19.2 – Provide 20 clean air/vanpool/ev spaces.  8%

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the plans and confirm that the correct number and configuration of “CLEAN AIR/VANPOOL/EV” parking stalls are included on the drawings.

 

On-Site Enforcement: The inspector should review the permit set of plans to verify that the correct number of clear air vehicle parking stalls have been provided and marked.


 

CALGreen Section: 5.710.6.3 Designated parking. For projects that add 10 or more vehicular parking spaces, provide designated parking for any combination of low-emitting, fuel- efficient, and carpool/van pool vehicles as shown in Table 5.106.2.2 of Division 5.1 based on the number of additional spaces.

 

5.106.5.2.1 Parking stall marking. Paint, in the paint used for stall striping, the following characters such that the lower edge of the last word aligns with the end of the stall striping and is visible beneath a parked vehicle:

 

CLEAN AIR/ VANPOOL/EV

 

Note:  Vehicles bearing Clean Air Vehicle stickers from expired HOV lane programs may be considered eligible for designated parking spaces.

 

 

Intent:

Change for 2012: The intent of this section and subsections requires additional designated

parking stalls when 10 or more parking spaces are added as part of an addition or alteration project, thus encouraging additional building occupants to use alternate forms of transportation to standard automobiles.

 

 

Compliance and Enforcement: See § 5.106.5.2 of this guide

CalGreen July 2012 Non-Residential: 5.106.8 Light pollution reduction

 Comments Off on CalGreen July 2012 Non-Residential: 5.106.8 Light pollution reduction
Dec 092012
 

5.106.8 Light pollution reduction.

IESNA TM‐15‐11 2011, TABLE 5.106.8 for allowable BUG ratings

CALGreen Section: 5.106.8 Light pollution reduction. Outdoor lighting systems shall be designed and installed to comply with the following:

 

1. The minimum requirements in the California Energy Code for Lighting Zones 1-4 as defined in Chapter 10 of the California Administrative Code; and

2. Backlight, Uplight and Glare (BUG) ratings as defined in IESNA TM-15-11; and

3. Allowable BUG ratings not exceeding those shown in Table 5.106.8, or  Comply with a local ordinance lawfully enacted pursuant to Section 101.7, whichever is more stringent.

 

Exceptions:

1.   Luminaries that qualify as exceptions in Section 147 of the California Energy Code

2.   Emergency lighting

 

Note:  See also California Building Code, Chapter 12, Section 1205.6 for college campus lighting requirements for parking facilities and walkways.

 

5.106.8.1 Effective date.  Newly constructed nonresidential projects with outdoor lighting for which an application for a building permit is submitted on or after July 1, 2012 shall comply with this section.

TABLE 5.106.8

[Table not shown for clarity, refer to Code]

Intent:

The intent of this code provision is to ensure that newly constructed projects reduce the amount of light and glare from both interior and exterior light sources leaving the site. This is to minimize light pollution in order to maintain our dark skies.

 

Change for 2012: This section is proposed to be moved from the voluntary Appendix A5 where it was located after modification in a recent emergency rulemaking. Problems with the version published in the 2010 code were identified as potential threats to public safety due to inadequate site illumination. In the intervening months between the emergency rulemaking and the effective date of the 2012 supplement, it should have been tested for utility and ease of compliance and enforcement as a voluntary standard when it becomes mandatory in its new format.

 


 

Existing Law or Regulation:

There are several existing codes that are being referenced in this provision as follows:

1. Lighting power requirements in the California Energy Code, CCR, Title 24, Part 6.

2. Lighting zone characteristics and lighting zones 1-4 as defined in Chapter 10 of the

CaliforniaAdministrative Code, CCR Title 24, Part 1.

3. California Building Code, CCR title 24, Part 2 Section 1205.6 exception regarding campus lighting for parking and walkways.

4. The latest standards of the Illuminating Engineers Society in TM-15-11.

 

 


Compliance Method:

FIRST:

Comply with California Energy Commission regulations in Part 1 and Part 6 cited above. Those standards form a basis upon which to build for the purpose of light pollution reduction in addition to energy efficiency. The provisions in Part 1 provide a weighted approach to the project site location, with a project located in the middle of a big city allowed more light to escape than a project at a rural or urban location. Part 6 addresses power and energy efficiency of outdoor lighting. There are exceptions for certain occupancies for lighting power requirements which would apply to this provision, but voluntary compliance with any or all of the items is encouraged.

 

THEN:

To comply with this provision, either:

1.   Consult and comply with a local dark skies ordinance, if more stringent than these regulations.

2.   Specify exterior lighting fixtures that meet IESNA TM-15-11 regarding backlight, up light and glare. Rating may not exceed those values shown in Table 5.106.8

 

Enforcement:

Plan Intake: The reviewer and/or plan checker should review the construction documents, including exterior light sources, to confirm compliance with Part 1, Part 2 and Part 6; review the electrical plans and specifications for complying building and exterior lighting, including photometric data for perimeter site lighting fixtures; and review specifications for any controls

to be installed on the project.

 

On-Site Enforcement: The inspector should review the permit set of plans to verify that all lighting and power calculations and specified products are installed as specified on the approved plans and specifications.

 

STATE OFCALIFORNIA– STATE AND CONSUMER SERVICES AGENCY                            GOVERNOR EDMUND G. BROWN JR.

 

 

BUILDING STANDARDS COMMISSION

2525 Natomas Park Drive, Suite 130

Sacramento,California95833-2936(916) 263-0916 FAX (916) 263-0959

 

 

 

 

BUILDING STANDARDS BULLETIN 11-02

 

 

DATE:              April 26, 2011

 

TO:                             LOCAL BUILDING OFFICIALS INTERESTED PARTIES

 

SUBJECT:     CHANGES TO THE CALIFORNIA GREEN BUILDING STANDARDS  ODE (CALGreen) REGARDING LIGHT POLLUTION REDUCTION

 

This bulletin is to bring attention to new requirements of the 2010 California Building Standards Code in Title 24, Part 11 of the California Code of Regulations (as also known as CALGreen). Specifically, the new requirement affects Chapter 5 – Nonresidential Mandatory Measures, Division 5.1, Section 5.106.8 Light pollution reduction.

 

The California Building Standards Commission (CBSC) at its April 19, 2011 meeting approved an emergency proposal submitted in response to a public petition regarding concerns over security aspects of the light pollution reduction provisions currently in effect in the 2010

CALGreen code.

 

The repealed language and modified language relocated to Appendix A5 via this emergency adoption, is reprinted herein for your reference. Please note that during the ensuing comment period which this provision is subject to, the language may be further amended.

 

Upon approval of the proposed emergency, the existing provisions in Section 5.106.8 were repealed and new requirements were approved. Proposed changes to the regulations include removal of language that presented public safety concerns and compliance difficulties in favor of referenced national standards.

 

This action corrects and simplifies the light pollution provisions and moves them to the voluntary appendix, with mandatory adoption delayed until July 1, 2012, to allow designers, builders and enforcing agencies time to adjust to the new standards. These emergency modifications were made within CBSC authority, with necessary amendments, and in the interest of public safety.

 

Should you have questions or further clarification is needed concerning this bulletin, please feel  free to contact our technical staff at (916) 263-0916 or through our contact e-mail address cbsc@dgs.ca.gov.

 

 

 

 

 

 

Dave Walls

Executive Director

 

(REPEAL LANGUAGE)

 

 

SECTION 5.106

SITE DEVELOPMENT

 

5.106.8 Light pollution reduction. Meet lighting power requirements in the California Energy Code, CCR, Title 24, Part 6, and design interior and exterior lighting such that zero direct-beam illumination leaves the building site. Comply with lighting zones 1-4 and lighting zone characteristics as defined in Chapter 10 of the California Administrative Code, CCR, Title 24, Part 1, using the following strategies:

1. Shield all exterior luminaires or provide cutoff luminaires per Section 132 (b) of the California Energy Code.

2. Contain interior lighting within each source.

3. Allow no more than .01 horizontal footcandles to escape 15 feet beyond the site boundary.

4. Automatically control exterior lighting dusk to dawn to turn off or lower light levels during inactive periods.

 

Exceptions:

1.                     CCR, Title 24, Part 2, Chapter 12, Section 1205.6 for campus lighting requirements for parking facilities and walkways

2.    Emergency lighting and lighting required for nighttime security

 

 

(NEW AMENDED LANGUAGE)

 

SECTION A5.106

SITE DEVELOPMENT

 

A5.106.8 Light pollution reduction. Outdoor lighting systems shall be designed and installed to comply with the following:

1.  The minimum requirements in the California Energy Code for Lighting Zones 1-4 as defined in Chapter 10 of the California Administrative Code; and

2.  Backlight, Uplight and Glare (BUG) ratings as defined in IESNA TM-15-07; and

3.  Allowable BUG ratings not exceeding those shown in Table A5.106.8, or

 

Comply with a local ordinance lawfully enacted pursuant to Section 101.7, whichever is more stringent.

 

Exceptions:

1.             Luminaires that qualify as exceptions in the California Energy Code

2.             Emergency lighting

 

Note:  See also California Building Code, Chapter 12, Section 1205.6 for college campus lighting requirements for parking facilities and walkways.

 

TABLE A5.106.8

Maximum Allowable Backlight, Uplight and Glare (BUG) Ratings1

 

 

Allowable Rating

Lighting

Zone 1

Lighting

Zone 2

Lighting

Zone 3

Lighting

Zone 4

Allowed Backlight Rating        
Greater than 2 mounting heights from property line B3 B4 B5 B5
1 – 2 mounting heights from property line and oriented

with B towards the property line

B2 B3 B4 B4
0.5 – 1 mounting height from property line and oriented with B towards the property line B1 B2 B3 B3
Less than 0.5 mounting height from property line adjacent to a street and oriented with B towards the property line2  

B0

 

B1

 

B2

 

B3

Less than 0.5 mounting height from property line and oriented with B towards the property line B0 B0 B1 B2
Allowed Uplight Rating U0 U1 U2 U3
Allowed Glare Rating2 G1 G2 G3 G4
Allowed Glare Rating, Building Mounted Luminaires3        
Greater than 2 mounting heights to any property line G1 G2 G3 G4
1 – 2 mounting heights to any property line G0 G1 G1 G2
0.5 – 1 mounting heights to any property line G0 G0 G1 G1
Less than 0.5 mounting height to any property line G0 G0 G0 G1

 

1 IESNA Lighting Zones 0 and 5 are not applicable; refer to Lighting Zones as defined in the California Energy Code and Chapter 10 of the California Administrative Code.

2 For purposes of compliance with this section, the property line may be considered to be the centerline of a public roadway or transit line. For properties adjacent to public walkways, bikeways, plazas and parking lots, the property line may be considered to be five feet beyond the site boundary.

3 Building-mounted luminaires that cannot be mounted with their backlight to the property line shall meet the Allowed Glare rating for all luminaires. Light from a building-mounted luminaire shall not exceed the Backlight rating in the direction of the property line.

 

Addendum A for IESNA TM-15-07: Backlight, Uplight, and Glare (BUG) Ratings

 

The following Backlight, Uplight, and Glare ratings may be used to evaluate luminaire optical performance related to light trespass, sky glow, and high angle brightness control. These ratings are based on a zonal lumen calculations for secondary solid angles defined in TM-15-07. The zonal lumen thresholds listed in the following three tables are based on data from photometric testing procedures approved by the Illuminating Engineering Society for outdoor luminaries (LM-31 or LM-35).

 

 

 

 

Table A-1: Backlight Ratings (maximum zonal lumens)

 

   

 

B0

 

 

B1

 

 

B2

 

 

B3

 

 

B4

 

 

B5

 

 

Backlight / Trespass

 

BH

 

110

 

500

 

1000

 

2500

 

5000

 

>5000

 

BM

 

220

 

1000

 

2500

 

5000

 

8500

 

>8500

 

BL

 

110

 

500

 

1000

 

2500

 

5000

 

>5000

 

Backlight Rating

Secondary Solid Angle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 


 

Table A-2: Uplight Ratings (maximum zonal lumens)

 

   

 

U0

 

 

U1

 

 

U2

 

 

U3

 

 

U4

 

 

U5

 

 

Uplight / Skyglow

 

UH

 

0

 

10

 

100

 

500

 

1000

 

>1000

 

UL

 

0

 

10

 

100

 

500

 

1000

 

>1000

 

FVH

 

10

 

75

 

150

 

>150

   
 

BVH

 

10

 

75

 

150

 

>150

   

 

Uplight Rating

Secondary Solid Angle

 

 

 

 

 

Table A-3: Glare Ratings (maximum zonal lumens)

 

Glare Rating for

   

 

G0

 

 

G1

 

 

G2

 

 

G3

 

 

G4

 

 

G5

 

Glare / Offensive Light

 

FVH

 

10

 

250

 

375

 

500

 

750

 

>750

 

BVH

 

10

 

250

 

375

 

500

 

750

 

>750

 

FH

 

660

 

1800

 

5000

 

7500

 

12000

 

>12000

 

BH

 

110

 

500

 

1000

 

2500

 

5000

 

>5000

 

Asymmetrical Luminaire Types (Type I, Type II, Type III, Type IV)

 

Secondary Solid Angle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Glare Rating for

   

 

G0

 

 

G1

 

 

G2

 

 

G3

 

 

G4

 

 

G5

 

Glare / Offensive Light

 

FVH

 

10

 

250

 

375

 

500

 

750

 

>750

 

BVH

 

10

 

250

 

375

 

500

 

750

 

>750

 

FH

 

660

 

1800

 

5000

 

7500

 

12000

 

>12000

 

BH

 

660

 

1800

 

5000

 

7500

 

12000

 

>12000

 

Quadrilateral Symmetrical Luminaire Types (Type V, Type V Square)

 

Secondary Solid Angle

 

Notes to Tables A-1, A-2, and A-3:

 

(1) Any one rating is determined by the maximum rating obtained for that table. For example, if the BH zone is rated B1, the BM zone is rated B2, and the BL zone is rated B1, then the backlight rating for the luminaire is B2.

 

(2) To determine BUG ratings, the photometric test data must include data in the upper hemisphere unless no light is emitted above 90 degrees vertical (for example, if the luminaire has a flat lens and opaque sides), per the IES Testing Procedures Committee recommendations.

 

(3) It is recommended that the photometric test density include values at least every

2.5 degrees vertically. If a photometric test does not include data points every 2.5 degrees vertically, the BUG ratings shall be determined based on appropriate interpolation.

 

(4) A “quadrilateral symmetric” luminaire shall meet one of the following definitions:

a.  A Type V luminaire is one with a distribution that has circular symmetry, defined by the IESNA as being essentially the same at all lateral angles around the luminaire.

b.  A Type VS luminaire is one where the zonal lumens for each of the eight horizontal octants (0-45, 45-90, 90-135, 135-180, 180-225, 225-270, 270-

315, 315-360) are within ±10 percent of the average zonal lumens of all octants.

 

“BUG” RATING EXAMPLE:

 

 

A 250-watt MH area luminaire, Type IV forward throw optical distribution. Based on the photometric test data, the luminaire has the following zonal lumen distribution:

 

Forward Light Lumens % Lamp Lumens
FL       (0 – 30 degrees)

1618

5.9%

FM      (30 – 60 degrees)

6093

22.2%

FH     (60 – 80 degrees)

3748

13.6%

FVH (80 – 90 degrees)

27

0.1%

Back Light    
BL    (0 – 30 degrees)

985

3.6%

BM   (30 – 60 degrees)

930

3.4%

BH    (60 – 80 degrees)

136

0.5%

BVH  (80 – 90 degrees)

16

0.1%

Uplight    
UL   (90 – 100 degrees)

0

0.0%

UH (100 – 180 degrees)

0

0.0%

 

 

Backlight Rating: Determine the lowest rating where the lumens for all of the secondary solid angles do not exceed the threshold lumens from Table A-1.  In this example the backlight rating would be B2 based on the BL lumen limit.

 

Uplight Rating: Determine the lowest rating where the lumens for all of the secondary solid angles do not exceed the threshold lumens from Table A-2.  In this example the uplight rating would be U1 based on the FVH and BVH lumen limits.

 

Glare Rating: Determine the lowest rating where the lumens for all of the secondary solid angles do not exceed the threshold lumens from Table A-3 for a Type IV distribution.  In this example, the glare rating would be G2 based on the FH lumen limit.

 

Therefore, the BUG rating for this luminaire would be:  B2  U1   G2